Enter the following command to initiate downloading via PC-Link – Section
[499]
[Installer Code] [499]
. Plugging in the PC-Link connec-
tor will automatically initiate the connection if DLS is initiated before connecting the PC-Link Header.
6HFWLRQ>@WR>@3URJUDPPDEOH2XWSXW$WWULEXWHV
These Sections are used to customize the operation of the PGM outputs (Section
[501]
for PGM 1, Section
[502]
for PGM 2 etc.). The available
options depend on which PGM output type is programmed. When the PGM Output Options (Section
[009]
to
[011]
) are programmed, the sys-
tem will change the PGM Attributes to the default settings. The PGM Attributes will default if a new PGM output option is programmed.
PGM Output Option [01], [03] to [08], [11] to [22], [25], [26], [28], [33],[34]
PGM Output Option [03], [19] to [22]
PGM Output Option [09]
PGM Output Option [10]
PGM Output Option [31]
Option
Description
[3]
ON
: The PGM output will operate normally (switch to ground when activated).
OFF:
The PGM output will be normally ground and switch to open collector (open circuit) when activated.
Option
Description
[4]
ON:
The PGM output will activate for the duration of the PGM Output Timer when the
[
][7][x]
command is performed.
OFF:
The PGM output will latch until the
[
][7][x]
command is performed again.
[5]
ON:
A valid user code must be entered after the
[
][7][x]
command.
OFF:
A user code is not required.
Option
Description
[1]
ON:
PGM output activates if a Service Required trouble condition is present.
[2]
ON:
PGM output activates if an AC trouble condition is present.
[3]
ON:
PGM output activates if a Telephone Line trouble condition is present.
[4]
ON:
PGM output activates if a Failure to Communicate trouble condition is present.
[5]
ON:
PGM output activates if a Zone Fault condition is present.
[6]
ON:
PGM output activates if a Zone Tamper condition is present.
[7]
ON:
PGM output activates if a Wireless Low Battery trouble condition is present.
[8]
ON:
PGM output activates if a Loss of Clock trouble condition is present.
Option
Description
[1]
ON:
PGM output activates if a Burglary Alarm occurs.
[2]
ON:
PGM output activates if a Fire Alarm occurs.
[3]
ON:
PGM output activates if a Panic Alarm occurs.
[4]
ON:
PGM output activates if a Medical Alarm occurs.
[5]
ON:
PGM output activates if a Supervisory Alarm occurs.
[6]
ON:
PGM output activates if a Priority Alarm occurs.
[7]
ON:
PGM output activates if a 24-Hour Hold-up Alarm occurs.
[8]
ON:
the PGM output activates for the time programmed for the PGM Output Timer.
OFF:
the PGM output will latch until a valid user code is entered.
If System Event PGM is programmed to follow the command output timer then all attributes must be enabled.
Option
Description
[1]
ON:
PGM output activates if a Fire Alarm occurs.
[2]
ON:
PGM output activates if a Panic Alarm occurs.
[3]
ON:
PGM output activates if a Burglary Alarm occurs.
[4]
ON:
PGM output activates if an Opening/Closing occurs.