PowerSeries - PC1616/PC1832/PC1864
36
>@>@=RQH$WWULEXWHV
=RQH$WWULEXWH'HIDXOWV< 2SWLRQ211 2SWLRQ2))
Attribute:
1
2
3
4
5
6
7
8
ON
Audible
Steady
Chime
Bypass
Force*
Swing
Tx. Delay
Wireless Zn
OFF
Silent
Pulsed
No
No
No
No
No
No
Zone Type:
00 Null Zone
N
N
N
N
N
N
N
N
01 Delay 1
Y
Y
Y
Y
N
Y
N
N
02 Delay 2
Y
Y
Y
Y
N
Y
N
N
03 Instant
Y
Y
Y
Y
N
Y
N
N
04 Interior
Y
Y
N
Y
N
Y
N
N
05 Int. Stay/Away
Y
Y
N
Y
Y
Y
N
N
06 Dly. Stay/Away
Y
Y
N
Y
Y
Y
N
N
07 Dly. 24hr Fire (Hardw.)
Y
N
N
N
N
N
N
N
08 Stand. 24hr Fire (Hardw.)
Y
N
N
N
N
N
N
N
09 24hr Superv.
N
Y
N
N
Y
N
N
N
10 24hr Superv. Buzzer
N
Y
N
Y
N
N
N
N
11 24hr Burglary
Y
Y
N
Y
N
N
N
N
12 24hr Holdup
N
Y
N
N
N
N
N
N
13 24hr Gas
Y
N
N
N
N
N
N
N
14 24hr Heating
Y
N
N
N
N
N
N
N
15 24hr Medical
Y
Y
N
N
N
N
N
N
16 24hr Panic
Y
Y
N
N
N
N
N
N
17 24hr Emergency
Y
Y
N
N
N
N
N
N
18 24hr Sprinkler
Y
Y
N
N
N
N
N
N
19 24hr Water
Y
Y
N
N
N
N
N
N
20 24hr Freeze
Y
Y
N
N
N
N
N
N
21 24hr Latching Tamper
Y
Y
N
N
N
N
N
N
22 Momentary Keyswitch
N
N
N
N
Y
N
N
N
23 Maintained Keyswitch
N
N
N
N
Y
N
N
N
25 Interior Delay
Y
Y
N
Y
N
Y
N
N
26 24hr Non-alarm
N
N
N
N
Y
N
N
N
29 Auto Verified Fire
Y
N
N
N
N
N
N
N
30 Fire Supervisory
N
N
N
N
N
N
N
N
31 Day Zone
Y
Y
N
Y
Y
Y
Y
N
32 Instant Stay/Away
Y
Y
N
Y
N
N
N
N
35 24 hr Bell/Buzzer
Y
Y
N
Y
N
Y
N
N
36 24-hr Non-Latching Tamper
N
Y
N
N
N
Y
N
N
37 Night Zone
Y
Y
N
Y
Y
Y
N
N
KU&20RQR[LGH
Y
N
N
N
N
N
N
N
KU&20RQR[LGH:/6
Y
N
N
N
N
N
N
Y
87 Dly. 24hr Fire (Wireless)
Y
N
N
N
N
N
N
Y
88 Stand. 24hr Fire (Wireless)
Y
N
N
N
N
N
N
Y
Attribute:
9
10
11
12
13
14
15
16
ON
Cross Zn
Zone Attributes 10-13 For Future Use
NC Loops
SEOL
DEOL
OFF
No
Config.
Config.
Config.
Zone Type:
00 Null Zone
N
N
N
N
N
N
N
N
01 Delay 1
N
N
N
N
N
N
N
N
02 Delay 2
N
N
N
N
N
N
N
N
03 Instant
N
N
N
N
N
N
N
N
04 Interior
N
N
N
N
N
N
N
N
05 Int. Stay/Away
N
N
N
N
N
N
N
N
06 Dly. Stay/Away
N
N
N
N
N
N
N
N
07 Dly. 24hr Fire (Hardw.)
N
N
N
N
N
N
N
N
08 Stand. 24hr Fire (Hardw.)
N
N
N
N
N
N
N
N
09 24hr Superv.
N
N
N
N
N
N
N
N
10 24hr Superv. Buzzer
N
N
N
N
N
N
N
N
11 24hr Burglary
N
N
N
N
N
N
N
N
12 24hr Holdup
N
N
N
N
N
N
N
N
13 24hr Gas
N
N
N
N
N
N
N
N
14 24hr Heating
N
N
N
N
N
N
N
N
15 24hr Medical
N
N
N
N
N
N
N
N
16 24hr Panic
N
N
N
N
N
N
N
N
17 24hr Emergency
N
N
N
N
N
N
N
N
18 24hr Sprinkler
N
N
N
N
N
N
N
N