The 4-wire KEYBUS (red, black, yellow and green) is the communication connection between the control panel and all modules. The
4 KEYBUS terminals of all modules must be connected to the 4 KEYBUS terminals of the main control panel.
The following rules must be followed when wiring the Keybus:
•
Minimum 22 AWG wire, maximum 18 AWG (2-wire twisted preferred
•
Do
NOT
use shielded wire
•
Modules can be home run, connected in series or can be T-tapped
provided that the maximum wire distance from the control panel to
any module does not exceed 305m
•
No more than 915m of wire can be used in total
=RQH:LULQJ
Zones can be wired for Normally Open, Normally Closed Contacts with
Single-end-of-line (SEOL) resistors or Double End-of-Line (DEOL)
resistors. Observe the following guidelines:
•
Minimum 22 AWG wire, maximum 18 AWG
•
Do
NOT
use shielded wire
•
Wire run resistance shall not exceed 100
. Refer to the chart:
•
Section
[001-004]
selects Zone Definition
•
Section
[013]
Opt
[1]
selects Normally Closed or EOL resistors
•
Section
[013]
Opt
[2]
selects Single EOL or Double EOL resistors
•
Section
[101]-[108]
Opt
[14], [15], [16]
selects Normally Closed Sin-
gle EOL or Double EOL for onboard zones (Zone 1-8)
Zone Status - Loop Resistance/Loop Status
• Fault
- 0
(shorted wire/loop)
• Secure
- 5600
(contact closed)
• Tamper
- infinite (broken wire, open)
• Violated
- 11,200
(contact open)
=RQH([SDQGHUV
Zone expanders add zones in groups
of eight to the Alarm system. Module
jumpers J1,J2,J3 are required to
assign zones to these modules.
Jumper settings for PC5108 v2 are
shown here.
• PC5108 v1.0 supports first 32
zones only.
• Do NOT use PC5108 v1 &v2 on the
same panel.
Module
Zones
Jumpers
Assigned
J1
J2
J3
ON
ON
ON
Zones Disabled
OFF ON
ON
Zones 09-16
ON
OFF ON
Zones 17-24
OFF OFF ON
Zones 25-32
ON
ON
OFF
Zones 33-40
OFF ON
OFF
Zones 41-48
ON
OFF OFF
Zones 49-56
OFF OFF OFF
Zones 57-64
Refer to the associated installation sheet for Jumper locations
for the PC5108.
%HOO:LULQJ
Bell Output Voltage: 12 VDC, -15%/+10% when input voltage is between 85-110% of rated value and output
current is 0.0A - 0.7A.
NOTE:
Steady, Pulsed alarms are also supported.
The Bell output is supervised and power limited by 2A PTC. If unused, connect a 1000
resistor across Bell+
and Bell- to prevent the panel from displaying a trouble. See [
][2] Trouble Display on page 8.
CONTROL
PANEL
76m
76m
152m
152m
Burglary Zone Wiring Chart
Wire
Gauge
Maximum wire Length to
End-of-line Resistor
(feet/meters)
22
3000 / 914
20
4900 / 1493
19
6200 / 1889
18
7800 / 2377
Figures are based on maximum wiring
resistance of 100 ohms.
Normally Closed Loops
Single End-of-Line Resistor Wiring
Double End-of-Line Resistor Wiring