PowerSeries Neo Installation Guide
UK Compliance Statement
In the UK this product is suitable for use in systems installed to conform to PD
6662:2017 at Grade 2 and environmental class 2 with the following notification
options: A, B, C, D.
The CIE and notification equipment should be located and supervised to minimize the
risk of vandalism or sabotage. It is preferable for the CIE, signaling and network
equipment to be located in an area where a confirmed activation will be generated.
HS2128, HS2064, HS2032, HS2016 are compliant with criteria for sequentially
confirmed intruder alarm systems as per Standard BS8243:2010+A1:2014.
For an alarm condition to be regarded as sequentially confirmed:
a) The HS2128, HS2064, HS2032, HS2016 should be configured so that at least two
separate alarm conditions are reported, each originating from an independent detector
within the confirmation time; Section [042] option 003 (Sequential Detection), section
[005]>[000], Burglary Verification Timer set to a value between 30 and 60.
b) The two detectors should either be of:
1) different technologies which are permitted to have overlapping areas of coverage; or
2) the same single technology and not have overlapping areas of coverage.
To be regarded as independent, each detector should be configured to report alarm
conditions separately to the HS2128, HS2064, HS2032, HS2016.
The HS2128, HS2064, HS2032, HS2016 are capable of supporting the completion of the
full setting procedure by one of the following methods:
a) push button switch mounted outside the supervised premises. Instructions to be
provided for the zone type to be programmed for the key arming; or
b) protective switch (i.e., door contact) fitted to the final exit door of the alarmed
premises or area. Use zone type 016 (Final Door Set) for the final exit door.
In this case the setting procedure is a two-stage process of initiating the setting
procedure within the supervised premises (e.g., using wireless key PG8929, PG8939,
PG8938, PG8949 or user code) followed by completion of setting by one of the two
methods described above.
This prohibits the use of a timed exit procedure.
If a protective switch (i.e. door contact) is used as the method of completion of setting,
then the keypad should be sited near to the final exit door so that the IAS can be unset
promptly. Where appropriate, additional internal audible indications (PG8911 indoor
sirens) should be provided so that persons within a building are informed that the
HS2128, HS2064, HS2032, HS2016 are due to be set. Additional keypads should be
provided, where appropriate, so that if the alarm panel is set there are means available
locally within the supervised premises to unset the system.
HS2128, HS2064, HS2032, HS2016 are capable of supporting the following unsetting
methods in accordance with BS8243:
6.4.2 Prevention of entry to the supervised premises before the HS2128, HS2064,
HS2032, HS2016 are unset. Unsetting using PG8929,PG8939, PG8938, PG8949
wireless key before entering the supervised premises causes or permits the initial entry
door to be unlocked. Program PGM1 or PGM2 in Section [009] to activate when system
is disarmed and release the mag-lock on the entry door.
- 19 -