background image

PowerSeries Neo Installation Guide

Additional Wiring

Zone Wiring

Power down the alarm controller and complete all zone wiring.

Zones can be wired to supervise normally open devices (e.g., smoke detectors) or
normally closed devices (e.g., door contacts). The alarm panel can also be
programmed for single end-of-line or double end-of-line resistors.

Zone programming is done using the following programming sections:

l

[001] selects zone definition

l

[013] Opt [1] for normally closed or EOL; Opt [2] for SEOL or DEOL

l

[201 - 208] partition assignment.

Observe the following guidelines when wiring zones:

l

For UL listed installations use SEOL or DEOL only

l

Minimum 22 AWG wire, maximum 18 AWG

l

Do not use shielded wire

l

Do not exceed 100

wire resistance. Refer to the following table:

Table 1-4 Burglary Zone Wiring Chart

Wire Gauge

Maximum Length to EOL Resistor (ft/-
meters)

22

3000 / 914

20

4900 / 1493

19

6200 / 1889

18

7800 / 2377

Figures are based on maximum wiring resistance of 100

Ω.

Aux Power Wiring

These terminals provide 11.3-12.5VDC/700mA of current (shared with PGM
outputs). Connect the positive side of any device to the AUX+ terminal, the
negative side to GND. The AUX output is protected; if too much current is
drawn from these terminals (wiring short) the output is temporarily shut off until
the problem is corrected.

Note:

If using a 12V, 14Ah battery, maximum AUX capacity for 24-hour

standby is 470mA.

PGM Wiring

Min/max operating voltages for devices, sensors and modules is 9.5VDC -
14VDC.

PGMs switch to ground when activated from the alarm controller. Connect the
positive side of the device to the AUX+ terminal and the negative side to a PGM
terminal.

PGM 1, 3, 4 supply up to 50mA; PGM 2 supplies up to 300mA.

A relay is required for current levels greater than 50mA or 300mA. PGM2 can
also be used for 2-wire smoke detectors, 24-hr burglary input alarm.

Note:

Use SEOL resistors on Fire zones only.

Figure 1-2 LED Output with Current Limiting Resistor and
Optional Relay Driver Output.

Single End-of-Line (SEOL) Resistor

When SEOL resistors are installed at the end of a zone loop, the alarm panel
detects if the circuit is secure, open, or shorted. The SEOL resistor must be

installed at the end of the loop for proper supervision.

To enable SEOL supervision, program section [013], options [1] and [2] to OFF.

Note:

This option should be selected if either normally closed or normally open

detection devices or contacts are used.

Figure 1-3 SEOL Wiring

Double End of Line (DEOL) Resistors

When double end-of-line (DEOL) resistors are installed at the end of a zone
loop, the second resistor enables the panel to determine if the zone is in open,
closed, tampered or faulted.

Note:

Any zone programmed for Fire or 24-hr Supervisory must be wired with a

SEOL resistor regardless of the type of zone wiring supervision selected for the
panel. If you change the zone supervision options from DEOL to SEOL or from
NC to DEOL, power the system down completely, then power it back up for
correct operation.To enable DEOL supervision, program section [013], option [1]
to OFF and option [2] to ON.

Figure 1-4 DEOL Wiring

Bell Wiring

These terminals supply 700mA of current at 10.4 - 12.5VDC for commercial/
residential installations. To comply with NFPA 72 Temporal Three Pattern
requirements, section [013] Opt [8] must be ON. Note that steady, pulsed alarms
are also supported.

Figure 1-5 Bell Wiring

The Bell output is supervised and power limited by 2A thermistor. If unused,
connect a 1000

resistor across Bell+ and Bell- to prevent the panel from

displaying a trouble.

Telephone Line Wiring

Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an RJ-31x
connector as indicated in the following diagram. For connection of multiple
devices to the telephone line, wire in the sequence indicated. Use 26 AWG wire
minimum for wiring.

- 4 -

Содержание DSC PowerSeries Neo

Страница 1: ...expander HSM2208 Power supply HSM2300 4 high current output expander HSM2204 Alternate communicator 3G2080E 3G2080RE TL280E TL280RE LE2080 R TL280LE R TL2803GE TL2803GRE TL8803G TL880LT TL880LE PCL 4...

Страница 2: ...e will only remove the mains power and will not disconnect battery power The installer is respons ible to ensure that a readily accessible mains disconnect device is incor porated in the building for...

Страница 3: ...e Corbus Current Calculation Chart For UL ULC and Commercial Listed applications the total standby and alarm current cannot exceed 700mA Table 1 2 Corbus Current Calculation Chart Item Current mA x Qu...

Страница 4: ...2 wire smoke detectors 24 hr burglary input alarm Note Use SEOL resistors on Fire zones only Figure 1 2 LED Output with Current Limiting Resistor and Optional Relay Driver Output Single End of Line SE...

Страница 5: ...e ID 804 001 716 Every wireless device has an ID printed on the sticker attached to the device The format is XXX YYYY where l XXX identifies the type or model of the device l YYYY is a short encrypted...

Страница 6: ...0 551 556 000 Set up partition account codes 310 001 008 Set up partition timers l Entry exit delay settle delay 005 001 008 l Automatic arming disarming schedule 151 158 001 002 l Auto disarming holi...

Страница 7: ...s 2 to enter the Trouble menu l On an LCD keypad scroll to a trouble type then press to view the spe cific trouble The zone name and trouble condition for each trouble are dis played on the screen l O...

Страница 8: ...ate communicator has stopped responding 10 Alt Comm FTC Trouble The alternate communicator has failed to communicate an internal event not generated by the panel Trouble 12 Not Networked Troubles 01 Z...

Страница 9: ...e l Battery capacity l 12 hours EN50131 l 24 hours INCERT Belgium Note For T 014 compliance INCERT certification only 14Ah 2x7Ah batteries were tested and are accepted for INCERT certified systems l M...

Страница 10: ...Times Partition 1 8 Entry Delay 1 030 sec Entry Delay 2 045 sec CP 01 030 sec Exit Delay 120 sec CP 01 060 sec Settle Delay 010 sec CP 01 000 sec 900 Bell Delay Partition Mask Y Y Y Y Y Y Y Y 901 Day...

Страница 11: ...ence Chime During Quick Exit Delay 8 Bell Squawk on Away Arm Disarm Only 018 System Options 6 1 Test Transmission Exception 2 Real Time Bypass Reporting 3 Armed State PGM ON at End of Exit Delay 4 Not...

Страница 12: ...er Lead OUT 03 DLS Lead IN 04 DLS Lead OUT 05 SA Lead IN 06 SA Lead OUT 07 Event Buffer 75 Full 313 Maintenance Events 3 01 Firmware Update Begin 02 Firmware Update Success 03 Firmware Update Fail 314...

Страница 13: ...0 102 Interval 1 End Time 0000 103 Interval 1 Days Assignment 01 Sunday 02 Monday 03 Tuesday 04 Wednesday 05 Thursday 06 Friday 07 Saturday 104 Interval 1 Holiday Assignment 09 Holiday 1 10 Holiday 2...

Страница 14: ...stem Information and Testing 900 System Information 000 Control Panel Version 001 016 Keypad 1 16 Version Info 101 116 8 HSM2108 1 16 Version Info 201 216 HSM2208 Version Information 460 Alternate Com...

Страница 15: ...011 012 013 014 015 016 017 018 019 020 021 022 023 024 025 026 027 028 029 030 031 032 033 034 035 036 037 038 039 040 041 042 043 044 045 046 047 048 049 050 051 052 053 054 055 056 057 058 059 060...

Страница 16: ...110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 Module Record Module Type Slot Serial Number Module Type Slot Serial Number Wireless Device Record Device Type Zone Serial...

Страница 17: ...on within the house Since many fires occur at night special attention should be given to the escape routes from sleeping quarters 3 Escape from a bedroom must be possible without opening the interior...

Страница 18: ...equipment as per EN50131 1 2006 A1 2009 EN50131 3 2009 EN50131 6 2008 A1 2014 Type A EN50136 1 1 1997 EN50136 2 1 EN50136 2 3 ATS2 Standards This device is suitable for use in systems with the followi...

Страница 19: ...hods a push button switch mounted outside the supervised premises Instructions to be provided for the zone type to be programmed for the key arming or b protective switch i e door contact fitted to th...

Страница 20: ...of merchantability or fitness for a particular purpose and of all other obligations or liabilities on the part of Digital Security Controls Digital Security Controls neither assumes responsibility fo...

Страница 21: ...tuation SOFTWARE PRODUCT LICENSE EULA The SOFTWARE PRODUCT is protected by copyright laws and international copyright treaties as well as other intellectual property laws and treaties The SOFTWARE PRO...

Страница 22: ...OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF DSC DSC MAKES NO OTHER WARRANTIES DSC NEITHER ASSUMES NOR AUTHORIZES ANY OTHER PERSON PURPORTING TO ACT ON ITS BEHALF TO MODIFY OR TO CHANGE THIS WARRA...

Страница 23: ...cipient agrees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT f Termination Without prejudice to any other ri...

Страница 24: ...ing pursuit of criminal prosecution wherever necessary All trademarks not owned by Tyco are the property of their respective owners and are used with permission or allowed under applicable laws Produc...

Отзывы: