PowerSeries Neo Installation Guide

HS2016: 2083333
HS2032: 1388888
HS2064/HS2128: 1052631
HS2064 E: 200000
HS2128 E: 100000

Warning Device Output

l

Integral sounder capable of 85 dB @ 3m, self-powered type Z

l

2 remote, wireless indoor/outdoor warning devices supported: models
PGX901 (indoor), PGX911 (outdoor) (X=4, 8, or 9)

l

Programmable as steady, pulsed or temporal three (as per ISO8201) and tem-
poral four (CO alarm) output

l

Warning device sounds alarms in the following priority: fire, CO, burg

Note:

For NFA2P certified systems the delay for operating the warning device

shall be set to max. 10 min.

Memory

l

CMOS EEPROM memory

l

Retains programming and system status on AC or battery failure for 20 years
min.

Power Supply - International

l

Input ratings: 220V-240Vac, 50/60Hz, 200mA

l

Transformer required, mounted in the same enclosure, permanently
connected

l

Transformer secondary ratings: 16.5Vac, 40VA min.

Note:

For installations using the transformer mounted inside the cabinet, replace

fuse only with the same type (20mm) rated 250V/315mA.

Regulated power supply:

l

1.7A regulated, supervised and integral to the control unit

l

Type A as per EN50131-6 Standard

l

700mA auxiliary supply, 12V DC

l

Positive temperature coefficient (PTC) for Bell, Aux+ and Battery terminals

l

Reverse battery detection/protection

l

Supervision for AC power and low battery

l

Normal and high current battery charge options

l

Supervised battery charging circuit

Current draw (panel):

l

85mA (nominal) 2A(Max)

Bell Output:

l

12V, 700mA supervised (1k Ohm) bell output (current limited at 2 amps)

l

Steady, Pulsed, Temporal 3 fire, Temporal 4 CO alarm cadences

l

Bell short detection (so hardware)

Aux+:

l

Voltage range = 9.6V - 13.8V DC

l

Current = 700mA (shared with Corbus R(ed))

l

Output ripple voltage: 270mVp-p max.

l

Onboard programmable outputs:

l

PGM 1 - 50mA switched programmable output

l

PGM 2 - 300mA current-limited switched programmable output. 2-Wire
smoke detectors (90mA current limited) are supported using this PGM

l

PGM 3 - 50mA switched programmable output

l

PGM 4 - 50mA switched programmable output

l

Hardware PGM over current protection

Battery

l

12V sealed lead acid, rechargeable

l

Battery capacity:

l

12 hours (EN50131),

l

24 hours INCERT [Belgium]

Note:

For T 014 compliance (INCERT certification), only 14Ah (2x7Ah)

batteries were tested and are accepted for INCERT certified systems.

l

Maximum standby time: 24 hours (with 14Ah battery and Aux current limited
to 470mA)

l

Recharging time to 80% 72 hours

l

Recharging rate: 240mA (12 hours max.), 480mA (24 hour backup)

l

Backup time: 24 hours

l

Battery lifespan: 3-5 years

l

Low battery trouble indication threshold 11.5VDC

l

Battery restore voltage 12.5V

l

Main board current draw (battery only):

l

HS2016/32/64/128 (no alternate communicator) standby 85mA DC

l

HS2016/32/64/128, (including alternate communicator) standby 190mA
DC

l

Transmit (alternate communicator module) 195mA DC

l

Resettable fuses (PTC) used on circuit board

l

Supervision for loss of primary power source (AC fail), battery loss or bat-
tery low voltage (battery trouble) with indication provided on the keypad

l

Internal clock locked to AC power frequency

Operating Environmental Conditions

l

Temperature range: EN= -10°C to 55°C (50°F-131°F)

l

Relative humidity: <93% non condensing

Alarm Transmitter Equipment (ATE) Specification

l

Digital dialer integral to the main control board

l

Supports SIA and Contact ID

l

Complies with TS203 021-1, -2, -3 Telecom equipment requirements and
EN50136-1-1, EN50136-2-1, EN50136-2-3 ATS 2

l

Optional Dual IP/Cellular communicators (3G2080(R)E/ TL2803G(R)E/
TL280(R)E) can be installed in the same enclosure and configured as
primary or back-up, with AES 128-bit encryption

l

Compliant with EN50136-1-1, EN50136-2-1 ATS2 requirements

System Supervision Features

The PowerSeries Neo continuously monitors a number of possible trouble
conditions and provides audible and visual indication at the keypad. Trouble
conditions include:

l

AC power failure

l

Zone trouble

l

Fire trouble

l

Telephone line trouble

l

Communicator trouble

l

Low battery condition

l

RF jam

l

AUX power supply fault

l

Failure to communicate

l

Module fault (supervisory or tamper)

Additional Features

l

2-way wireless device support

l

Visual verification ( audio)

l

Proximity tag support

l

PGM scheduling

l

Quick arming

l

User, partition, module, zone and system labels

l

Soak test

l

Programmable system loop response

l

Keypad and panel software versions viewable through keypad

l

Doorbell zone type

l

Low battery PGM type

- 9 -

Содержание DSC PowerSeries Neo

Страница 1: ...expander HSM2208 Power supply HSM2300 4 high current output expander HSM2204 Alternate communicator 3G2080E 3G2080RE TL280E TL280RE LE2080 R TL280LE R TL2803GE TL2803GRE TL8803G TL880LT TL880LE PCL 4...

Страница 2: ...e will only remove the mains power and will not disconnect battery power The installer is respons ible to ensure that a readily accessible mains disconnect device is incor porated in the building for...

Страница 3: ...e Corbus Current Calculation Chart For UL ULC and Commercial Listed applications the total standby and alarm current cannot exceed 700mA Table 1 2 Corbus Current Calculation Chart Item Current mA x Qu...

Страница 4: ...2 wire smoke detectors 24 hr burglary input alarm Note Use SEOL resistors on Fire zones only Figure 1 2 LED Output with Current Limiting Resistor and Optional Relay Driver Output Single End of Line SE...

Страница 5: ...e ID 804 001 716 Every wireless device has an ID printed on the sticker attached to the device The format is XXX YYYY where l XXX identifies the type or model of the device l YYYY is a short encrypted...

Страница 6: ...0 551 556 000 Set up partition account codes 310 001 008 Set up partition timers l Entry exit delay settle delay 005 001 008 l Automatic arming disarming schedule 151 158 001 002 l Auto disarming holi...

Страница 7: ...s 2 to enter the Trouble menu l On an LCD keypad scroll to a trouble type then press to view the spe cific trouble The zone name and trouble condition for each trouble are dis played on the screen l O...

Страница 8: ...ate communicator has stopped responding 10 Alt Comm FTC Trouble The alternate communicator has failed to communicate an internal event not generated by the panel Trouble 12 Not Networked Troubles 01 Z...

Страница 9: ...e l Battery capacity l 12 hours EN50131 l 24 hours INCERT Belgium Note For T 014 compliance INCERT certification only 14Ah 2x7Ah batteries were tested and are accepted for INCERT certified systems l M...

Страница 10: ...Times Partition 1 8 Entry Delay 1 030 sec Entry Delay 2 045 sec CP 01 030 sec Exit Delay 120 sec CP 01 060 sec Settle Delay 010 sec CP 01 000 sec 900 Bell Delay Partition Mask Y Y Y Y Y Y Y Y 901 Day...

Страница 11: ...ence Chime During Quick Exit Delay 8 Bell Squawk on Away Arm Disarm Only 018 System Options 6 1 Test Transmission Exception 2 Real Time Bypass Reporting 3 Armed State PGM ON at End of Exit Delay 4 Not...

Страница 12: ...er Lead OUT 03 DLS Lead IN 04 DLS Lead OUT 05 SA Lead IN 06 SA Lead OUT 07 Event Buffer 75 Full 313 Maintenance Events 3 01 Firmware Update Begin 02 Firmware Update Success 03 Firmware Update Fail 314...

Страница 13: ...0 102 Interval 1 End Time 0000 103 Interval 1 Days Assignment 01 Sunday 02 Monday 03 Tuesday 04 Wednesday 05 Thursday 06 Friday 07 Saturday 104 Interval 1 Holiday Assignment 09 Holiday 1 10 Holiday 2...

Страница 14: ...stem Information and Testing 900 System Information 000 Control Panel Version 001 016 Keypad 1 16 Version Info 101 116 8 HSM2108 1 16 Version Info 201 216 HSM2208 Version Information 460 Alternate Com...

Страница 15: ...011 012 013 014 015 016 017 018 019 020 021 022 023 024 025 026 027 028 029 030 031 032 033 034 035 036 037 038 039 040 041 042 043 044 045 046 047 048 049 050 051 052 053 054 055 056 057 058 059 060...

Страница 16: ...110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 Module Record Module Type Slot Serial Number Module Type Slot Serial Number Wireless Device Record Device Type Zone Serial...

Страница 17: ...on within the house Since many fires occur at night special attention should be given to the escape routes from sleeping quarters 3 Escape from a bedroom must be possible without opening the interior...

Страница 18: ...equipment as per EN50131 1 2006 A1 2009 EN50131 3 2009 EN50131 6 2008 A1 2014 Type A EN50136 1 1 1997 EN50136 2 1 EN50136 2 3 ATS2 Standards This device is suitable for use in systems with the followi...

Страница 19: ...hods a push button switch mounted outside the supervised premises Instructions to be provided for the zone type to be programmed for the key arming or b protective switch i e door contact fitted to th...

Страница 20: ...of merchantability or fitness for a particular purpose and of all other obligations or liabilities on the part of Digital Security Controls Digital Security Controls neither assumes responsibility fo...

Страница 21: ...tuation SOFTWARE PRODUCT LICENSE EULA The SOFTWARE PRODUCT is protected by copyright laws and international copyright treaties as well as other intellectual property laws and treaties The SOFTWARE PRO...

Страница 22: ...OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF DSC DSC MAKES NO OTHER WARRANTIES DSC NEITHER ASSUMES NOR AUTHORIZES ANY OTHER PERSON PURPORTING TO ACT ON ITS BEHALF TO MODIFY OR TO CHANGE THIS WARRA...

Страница 23: ...cipient agrees to the terms of this EULA If the SOFTWARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTWARE PRODUCT f Termination Without prejudice to any other ri...

Страница 24: ...ing pursuit of criminal prosecution wherever necessary All trademarks not owned by Tyco are the property of their respective owners and are used with permission or allowed under applicable laws Produc...

Отзывы: