SECTION V
3-1-2010
Page 5-8
DISCHARGE PIPING (AFTER REGULATORS)
(Continued)
Installation of Water Tank Pressurization Piping
Water tank pressurization is accomplished using the
factory-set water pressure regulator attached to the high
pressure manifold.
1. Install piping from the water pressure regulator to the
water tank location as shown in Figure 10.
Note:
Piping should include a master shut-off valve, a
relief valve, and a manifold.
2. For each water tank, verify that the flow arrow on the
check valve at the tank pressurization inlet is pointing
towards the tank.
3. Connect each tank to the manifold using a flexible hose
(Part No. 72584) and adapter fitting (Part No. 25582).
Attach swivel adapter to the manifold. Attach flexible
hose to the water tank assembly. Connect flexible hose
to the swivel adapter on the manifold.
Note:
A maximum of four 50 gal (189 L) water tanks
can be pressurized with a single regulator. For systems
requiring more than one regulator, regulators must be
piped in parallel to a common water tank pressurization
manifold. For one water pressure regulator, use 3/8 in.
piping. For two water pressure regulators, use 1/2 in.
piping.
FIGURE 10
008521
Installation of Water Discharge Piping
The water discharge piping connects the tanks to the atom-
izers according to the piping layout determined in the
design of the system.
1. Manifold the outlets of the tanks together using
selected discharge pipe size as determined in the
system calculations. See Figure 11.
2. Install water shut off valve to the outlet of the manifold.
Note:
For 3/4 in. pipe, use the 3/4 in. shut-off valve
(Part No. 435805). For pipe sizes greater than 3/4 in.,
use the 1 1/2 in. shut-off valve (Part No. 437341).
3. Install remaining pipe according to the piping layout
determined in the system design.
4. Using a compressed gas supply, blow-out the entire
water discharge piping assembly to remove any foreign
particles prior to connecting the atomizer.
5. Connect pipe to the atomizers using the 1/2 in. NPT
inlet connection on the atomizer.
FIGURE 11
008522
DISCHARGE MANIFOLD
SIZE ACCORDING TO
SYSTEM CALCULATIONS
MASTER SHUT OFF VALVE
(SEE COMPONENT SECTION)
WATER TANK
ASSEMBLY
UNION FOR
CONNECTION TO
REMAINING PIPE
WATER PRESSURE
REGULATOR (PART NO. 472014)
PIPING TO TANK
LOCATION
RELIEF VALVE
(PART NO. 436666)
SEE DETAIL F
SEE DETAIL G
ADAPTER
FITTING
(PART NO.
25582)
DETAIL F
SCALE 0.250
FLEXIBLE
HOSE
(PART NO.
72584)
DETAIL G
SCALE 0.250
NOTE: DIRECTION
OF ARROW IS
TOWARD TANK
FLEXIBLE
HOSE (PART
NO. 72584)
SHUT-OFF
VALVE (PART
NO. 437347)
Installation
Содержание ANSUL AQUASONIC
Страница 84: ...SECTION V 3 1 2010 Page 5 14 NOTES Installation ...
Страница 88: ...SECTION VII 3 1 2010 Page 7 2 Inspection NOTES ...
Страница 94: ...SECTION VIII 3 1 2010 Page 8 6 NOTES Maintenance ...
Страница 116: ...APPENDIX C 3 1 2010 Page C 2 Main and Reserve Systems NOTES ...
Страница 134: ...APPENDIX D 3 1 2010 Page D 18 008567 Typical Examples ...
Страница 135: ...APPENDIX D 3 1 2010 Page D 19 008568 Typical Examples ...
Страница 136: ...APPENDIX D 3 1 2010 Page D 20 008569 Typical Examples ...
Страница 137: ...APPENDIX D 3 1 2010 Page D 21 008570 Typical Examples ...
Страница 138: ...APPENDIX D 3 1 2010 Page D 22 008571 Typical Examples ...
Страница 139: ...APPENDIX D 3 1 2010 Page D 23 008572 Typical Examples ...
Страница 140: ...APPENDIX D 3 1 2010 Page D 24 008573 Typical Examples ...
Страница 141: ...APPENDIX D 3 1 2010 Page D 25 008574 Typical Examples ...