![Tyco Fire Suppression & Building Products ANSUL AQUASONIC Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/tyco-fire-suppression-and-building-products/ansul-aquasonic/ansul-aquasonic_design-installation-recharge-and-maintenance-manual_1186438027.webp)
System Components
3-1-10
Page 1-19
TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, MARINETTE, WI 54143
Form No. F-2010049 Copyright © 2010 Tyco Fire Suppression & Building Products. All rights reserved.
Pressure Switch – DPDT – Explosion-Proof
Description
The pressure switch is operated by the nitrogen agent pres-
sure when the system is discharged. The pressure switch
can be used to open or close electrical circuits to either
shut down equipment or turn on lights or alarms. The
double pole, single throw (DPST) pressure switch is
constructed with a gasketed, water tight housing. The
housing is constructed of malleable iron, painted red. A
1/4 in. NPT pressure inlet is used to connect the 1/4 in. pipe
from the AQUASONIC system.
The pressure switch can be installed either before or after
the pressure reducer in the distribution piping.
Minimum operating pressure is 50 psi (3.5 bar).
Shipping Assembly
Part No.
Description
43241
Pressure switch – DPDT
Component
Material
Thread Size/Type
Electrical Rating
Approvals
Pressure Switch
Housing:
Conduit Inlet: 3/4 in. NPT Female
10A - 125 VAC
FM Approved
DPDT
Malleable Iron
Pressure Inlet: 1/4 in. NPT Female
5A - 250 VAC
1/4 IN. PIPE CONNECTION
TO CYLINDERS
1/4 IN. UNION
3/8 IN. X 1/4 IN. BUSHING
NAMEPLATE
2 11/32 IN.
MOUNTING HOLES
7 7/8 IN.
(20 cm)
6 1/2 IN.
(16.5 cm)
5 3/16 IN.
(14.7 cm)
5 1/8 IN.
(13 cm)
3 9/16 IN.
(9 cm)
5 5/8 IN.
(14.2 cm)
2 5/8 IN.
(6.6 cm)
3/4 IN.
CONDUIT
OUTLET
000454
3/4 IN.
CONDUIT
OUTLET
Note:
Suitable for hazardous locations, Class I, Division I, Groups C, D,
and Class II, Division I, Groups E, F, G.
Содержание ANSUL AQUASONIC
Страница 84: ...SECTION V 3 1 2010 Page 5 14 NOTES Installation ...
Страница 88: ...SECTION VII 3 1 2010 Page 7 2 Inspection NOTES ...
Страница 94: ...SECTION VIII 3 1 2010 Page 8 6 NOTES Maintenance ...
Страница 116: ...APPENDIX C 3 1 2010 Page C 2 Main and Reserve Systems NOTES ...
Страница 134: ...APPENDIX D 3 1 2010 Page D 18 008567 Typical Examples ...
Страница 135: ...APPENDIX D 3 1 2010 Page D 19 008568 Typical Examples ...
Страница 136: ...APPENDIX D 3 1 2010 Page D 20 008569 Typical Examples ...
Страница 137: ...APPENDIX D 3 1 2010 Page D 21 008570 Typical Examples ...
Страница 138: ...APPENDIX D 3 1 2010 Page D 22 008571 Typical Examples ...
Страница 139: ...APPENDIX D 3 1 2010 Page D 23 008572 Typical Examples ...
Страница 140: ...APPENDIX D 3 1 2010 Page D 24 008573 Typical Examples ...
Страница 141: ...APPENDIX D 3 1 2010 Page D 25 008574 Typical Examples ...