RSLogix 5000 Sample (continued)
Figure 5 .1 shows the two configuration screens when setting up a message instruction to communicate with a RM-89 on a
DeviceNet network .
1) Message Type: Always “CIP Generic” .
2) Service Type: Depends on what you are accomplishing with the instruction . Setting the Service Type to Custom
will allow you to set the Service Code field . Otherwise, the Service Code will automatically update when you
change the Service Type .
3) Class: Always 23
hex
if you have to set it yourself . Other classes are used, but they will be automatically set when
you select the appropriate Service Type .
4) Instance: Usually “1” . Set to “0” when issuing a Reset, Save to Flash, or Restore from Flash command .
5) Attribute: Depends on what you are accomplishing with the instruction .
6) Source Element: The data source if you are writing data down to the RM-89 .
7) Source Length: The length of the data you are writing down to the RM-89
8) Path: Data path to the RM-89 . The path has the format {Scanner Name}“, ” <Scanner Port> “, ” <RM-89 MAC
address>, where {Scanner Name} is a string and <Scanner Port> and <RM-89 MAC address> are numeric values .
The [Tag] tab lists the tag used to control the message instruction . This tag must have a “MESSAGE” data type .