Adding the RM-89 to a Scan List (continued)
Output Tab
The Output tab is used to map where the output data for the RM-89 appears in the scanner’s data table .
You can choose not to map data to your RM-89 . If you do this, you will have to use explicit messaging to send commands
to the RM-89 . Depending on the application, this may actually simplify your ladder logic but at a cost of less efficient data
transfer over the DeviceNet network .
Saving the Scan List
Once the RM-89 is added to your scanner, the next step is to save the network configuration .
In RSNetWorx for DeviceNet, click on File -> Save .
Navigate to a directory that will be available to your RSLogix software, type in a meaningful name for your network and save
the file . A file with a “ .dnt” extension will be created .
Downloading the Scan List to the Scanner
Once the scan list is configured correctly, you must download it to the scanner .
1) Go online with the scanner . Click on
Network
in the menu bar and then select
Online
. The software will scan the
network and then go online . This process may take several minutes .
2) Once online, click on
Network
in the menu bar and then select
Download to Network.
The software will download
the new scan list to your scanner .