Saving Parameter Values
Parameter values can be stored in non-volatile Flash memory from within RSNetWorx by using the Class Instance Editor . To
open the Class Instance Editor:
• Go online with the network if necessary by clicking on Network in the menu bar and then selecting Online .
The software will scan the network and then go online . This process may take several minutes
• Click on the RM-89 in the graph window .
• Click on “Device” in the menu bar and then select “Class Instance Editor” .
The Class Instance Editor opens as is shown in figure 3 .3 .
1) In the Service Code section of the window, click on the
Description
drop down list, select the “Save”
option . The
Value
field will change to “16” .
2) In the Object Address section, set Class: to a value of “23” and
Instance
: to a value of “0” . Also, make sure
the
Send the Attribute ID
checkbox is unchecked .
3) Click on the [Execute] button . The RM-89 will respond with the message “The execution was completed”
in the
Receive Data
text box .
Figure 3 .3 Class Instance Editor