TruSteel AutoVap30 User Manual | | v. 1.9
15 / 39
PUMP CONTROLS
STEP 1: SET PUMP LOCKOUT SETPOINTS
In this section you will be able to change and set your parameters for your lockouts. If the system
is running within range of your parameters, then it will continue to run until you manually stop the
system. If a parameter goes out of the setpoint range, the feed pump will automatically stop.
Procedures
1.
Open the PUMP CONTROL Screen
Locate PUMP CONTROL on the HMI Home Screen and press on the button to open
the PUMP CONTROL Screen.