background image

Thermostatic bar mixer shower

15

IN-SERVICE TESTING

Maintenance of the unit is required to give 
continued performance after installation and that 
it continues to provide scald prevention.

Note: A thermostatic mixing valve in need of 
maintenance can be undetectable in normal 
use and only becomes apparent when a 
disruption occurs in the hot or cold water supply 
temperatures or pressures.

Purpose

The purpose of in-service tests is to regularly 
monitor and record the performance of the 
thermostatic mixing valve. Deterioration in 
performance can indicate the need for service 
work on the valve and/or the water supplies. 

Procedure

Using the same measuring equipment or 
equipment to the same specification as used 
in the commissioning of the valve, adjust the 
temperature of the mixed water in accordance 
with the manufacturer’s instructions and the 
requirement of the application. Carry out the 
following sequence:

a)  Record the temperature of the hot and cold 

water supplies.

b)  Record the temperature of the mixed water 

at the largest draw-off flow rate.

c)  Record the temperature of the mixed water 

at a smaller draw-off flow rate, which shall be 
measured.

If the mixed water temperature has changed 
significantly from the previous test results 
(e.g.> 1 K) 5), record the change and before 
re-adjusting the mixed water temperature check 
that:

a)  that any in-line or integral strainers are clean,

b)  any in-line or integral check valves or other 

anti-back siphonage devices are in good 
working order,

c)  any isolating valves are fully open.

With an acceptable mixed water temperature, 
complete the following procedure:

a)  Record the temperature of the hot and cold 

water supplies.

b)  Record the temperature of the mixed water 

at the largest draw-off flow rate.

c)  Record the temperature of the mixed water 

at a smaller draw-off flow rate, which shall be 
measured.

d)  Isolate the cold water supply to the 

mixing valve and monitor the mixed water 
temperature.

e)  Record the maximum temperature achieved 

as a result of (d) and the final stabilised 
temperature.

f)  Record the equipment, thermometer etc. 

used for the measurements.

If at step (e) the final mixed water temperature 
is greater than the values in Table 17 and / 
or the maximum temperature exceeds the 
corresponding value from the previous results by 
more than about 2 K, the need for service work 
is indicated 

NOTE:

 In-service tests should be carried out 

with a frequency, which identifies a need 
for service work before an unsafe water 
temperature can result. In the absence of any 
other instruction or guidance, the procedure 
described in Annex F of D 08 may be used.

Annex F of D 08 (informative) 

Содержание ELINA

Страница 1: ...EL 024 7637 8321 INSTALLATION AND OPERATING INSTRUCTIONS Please read this book thoroughly and familiarise yourself with all instructions before commencing installation and keep it for future reference...

Страница 2: ...mation CONTENTS Page MAIN COMPONENTS 1 INTRODUCTION 2 3 TYPICAL COMMERCIAL INSTALLATIONS 4 INSTALLATION 5 8 PREPARING THE SHOWER 5 SITING OF THE SHOWER 5 SUPPLY PIPEWORK 5 STRAIGHT FITTINGS 6 MAKING G...

Страница 3: ...Thermostatic bar mixer shower 1 MAIN COMPONENTS Ref Description 1 Elina bar mixer valve bottom exit 2 Straight connector X2 3 Bar Bracket push fit X2 if supplied with your product 1 Fig 1 2 3...

Страница 4: ...can provide nominally equal pressures at the mixer shower Water Minimum Flow Rate For best performance within the specified running pressure range a minimum flow of 8 litres per minute should be avail...

Страница 5: ...s not flushed through before fitting Commercial Applications It is recommended that for all commercial applications easily accessible in line filters are used to aid maintenance Hard Water Areas a If...

Страница 6: ...after the appliance reducing valve it will be necessary to fit an additional drop tight pressure reducing valve when the mains pressure is over 5 bar The drop tight pressure reducing valve MUST be set...

Страница 7: ...r fixing to a laminate cubicle or panel SITING OF THE SHOWER ACCESSORIES Refer to fig 4 for correct siting of the shower The mixer shower should be positioned as detailed with all controls within comf...

Страница 8: ...S The supply pipes can be routed from the side rising rear or falling and must end in suitable fittings to accept the long thread connectors fig 5 The straight connectors can be used to connect to BSP...

Страница 9: ...tions supplied with it FLOW REGULATION IMPORTANT Make sure that all supply pipework has been flushed through before fitting the mixer and flow regulators A flow regulator is supplied for use with high...

Страница 10: ...is may vary should be positioned so that it is at the 12 o clock position If fitted correctly the graphic and flow control should now be sitting in the designed OFF position Once in place fit the reta...

Страница 11: ...maximum temperature of 41 C and should be checked on site to guarantee user safety After setting the maximum temperature turn the shower on and off several times and check the maximum setting is corr...

Страница 12: ...erature setting Allow the shower to run at this maximum temperature setting until the water temperature has stabilised Rotate the temperature control until your desired maximum showering temperature i...

Страница 13: ...tish Burns Association recommends 37 C to 37 5 C as a comfortable bathing temperature for children In premises covered by the Care Standards Act 2000 the maximum mixed water outlet temperature is 43 C...

Страница 14: ...he water flow rotate the flow control clockwise until the water stops flowing fig 12 To adjust the water temperature rotate the temperature control right hand side clockwise for a cooler shower or ant...

Страница 15: ...0 This can be found laser marked onto the body of the mixer valve PRODUCT FLOW RATES For guidance only Flow Rate l m 3 5 5 4 7 4 8 9 10 0 15 0 22 0 26 6 30 8 34 6 Pressure bar 0 1 0 2 0 3 0 4 0 5 1 0...

Страница 16: ...Thermostatic bar mixer shower 14 296 00 1 2 BSP 49 00 5 0 5 0 3 4 BSP 185 00 150 00 All dimensions listed in this fitting book regarding the product and installation are approximate DIMENSIONS...

Страница 17: ...y from the previous test results e g 1 K 5 record the change and before re adjusting the mixed water temperature check that a that any in line or integral strainers are clean b any in line or integral...

Страница 18: ...r temperatures are recorded in only one of these periods necessitating adjustment of the mixed water temperature then the next in service test can be deferred to 24 to 28 weeks after commissioning c I...

Страница 19: ...ERVICE TESTING RECORD Where installed Mixer valve location Date installed Installed by Commissioning details Hot water Temp C Pressure Bar Cold water Temp C Pressure Bar Maximum temperature setting Te...

Страница 20: ...ery three months and clean if necessary b Perform a thermal shut off test every three months and check the maximum temperature setting See the Commissioning section for the details of this test and re...

Страница 21: ...d 2 6 Flow regulator not fitted HP systems only 3 1 Flow regulators not fitted 1 1 1 Refer to the Commissioning section 1 2 1 Reposition temperature control knob 1 3 1 Reposition temperature control k...

Страница 22: ...t the inlet filters Clean if necessary 4 3 1 Turn off the shower and consult a suitably competent plumber 4 4 1 Clean shower head 4 5 1 Reduce the simultaneous demand 4 5 2 Make sure stop service valv...

Страница 23: ...Thermostatic bar mixer shower 21...

Страница 24: ...ent of a pro forma invoice by cheque or postal order Telephone orders are based on information given during the call Before contacting Triton please verify your requirements using the Information cont...

Отзывы: