Wire termination
Check the terminal cover fits. Adjust
wiring if necessary.
Fix the HP Input wiring to the terminals
with the supplied fasteners.
Note:
Bolts must sit on top of the lugs
facing to the back of the charger with the
nut at the back of the terminal to enable
the terminal covers to fit correctly.
Fix the grounding wire to the M8 earth
terminal and secure with supplied M8 nut.
For auxiliary field wiring termination go to
the appropriate section.
The wiring in label is located on the inside
of the left hand hinged side panel.
CRITICAL
You must use a torque wrench to tighten
to the specified tightening torque, and
you must apply a torque mark to the
stud and nut.
Tightening Torque
Terminal connections: 20Nm
Earth wire: 20Nm
Auxiliary field wiring
Refer to the Auxiliary field wiring section
for information regarding adding optional
safety features to the RTM-75kW.
CRITICAL
Wiring of the charger is to be done by
qualified electrical personnel only.
If a cable with neutral is used (i.e. when
doing a Veefil-RT 50kW replacement),
ensure the appropriate regulations are
followed to safely terminate the un-used
neutral cable. This must be done by
qualified electrical personnel only.
AC Input wiring
Ensure that the lugs and connection
points are clean and free of dirt before
you make the connections.
Place the supplied Ferrite over the HP
Input wiring only, and bend the wiring as
shown to ensure the terminal covers can
be re-attached.
20Nm
MAXIMUM TORQUE 20Nm
L2
REINSTALL TERMINAL COVERS.
L3
L1
FERRITE