9
TRI153.INS.046.3 - 08 March 2021
RTM - 75kW User Unit Installation Manual
www.tritium.com.au
Veefil®isaregisteredtrademarkofTritiumPtyLtd.©2021TritiumPtyLtd
Power supply preparation
Use 50mm flexible conduit for providing
power above ground.
Leave a minimum of 1500mm of conduit
and wiring from the right rear foundation
hole. Prior to installation, the conduit and
wiring will require trimming.
Minimum 1500mm
Charger front
Full conduit installation
Cut the conduit 400mm from the right
rear foundation hole. Cut the wiring as
shown below.
Note:
This installation is not suited to
route ethernet wiring.
Cut conduit
470mm from
foundation hole
AUX Field
wiring
1050mm
HP Input
Grounding
785mm
Charger front
Cable gland installation
Cut the conduit 100mm from the right
rear foundation hole. Cut the wiring as
shown below.
Cut conduit
100mm from
foundation hole
AUX
Field
wiring
1050mm
HP Input
Grounding
Ethernet
785mm
Charger front
Note:
Use expanding foam to fill in the
conduit to avoid it filling with water and
debris.
Site preparation - Above ground wiring