To discourage unauthorized changing of Aquastat settings, a
•
procedure to enter the adjustment mode is required. To enter
the adjustment mode, press the UP, DOWN, and I buttons (see
Figure #22
) simultaneously for three (3) seconds. Press the ‘I’
button until the feature requiring adjustment is displayed:
High limit
°F -- °C
Then press the UP and/or DOWN buttons to move the set
•
point to the desired value. After 70 seconds without any button
inputs, the control will automatically return to the READ mode.
II.
Display:
In the RUN mode
, the Aquastat will flash “bt” (boiler temp.) followed
by the water temperature (i.e., 220), followed by °F or °C. To read
boiler settings, press the “I” key to read the parameter of interest. For
example, press I and HL (High Limit) is displayed, followed by a three-
digit number, i.e., 220, followed by °F or °C. See
Table 9
for Display
Readout Definitions.
After approximately 60 seconds without any key pressed, the display
will enter a dim display mode. To return to the bright display mode,
simply press any key.
Control Operating Characteristics
The L7248A can be in any three (3) operational states: Normal, High
Limit and Error. The controller moves back and forth from High-
Limit to Normal state as part of normal operation. The controller
will enter the Error state when there is an abnormal condition. The
operating states are:
Normal: Boiler temperature has dropped below the high limit
•
setting (minus the differential) and has not exceeded the high
limit setting.
High-Limit: Boiler temperature has risen above the high limit
•
setting and has not dropped below the high limit setting (minus
the differential).
Error: The controller has detected an error condition (e.g., open
•
sensor) and has shut down the burner output. The controller
continues to monitor the system and automatically restarts if
the error condition clears. See
Table 10
.
For aquastat troubleshooting, see end of manual.
taBLE 10: ERROR cODES
Error
Code Cause / Action
Err1
Sensor fault; check sensor.
Err2
ECOM fault; check EnviraCOM wiring.
Err3
Hardware fault; replace control.
Err4
B1 fault; check B1 wiring/voltage
Err5
Low Line; check L1-L2; 110 VAC
Err6
Fuse; check ECOM wires, replace fuse
Err7
EEPROM,HL,LL,LDF;reset to default val
-
ues. Restore desired settings.
Err8
Repeated B1 fault (voltage present at B1
when output is turned off); check B1 wiring/
voltage
The operating sequence for L7248A is described next and shown
•
in
Table 11
.
TABLE 9: AQUASTAT DISPLAY
TEXT
DESCRIPTION
DISPLAY
bt
Boiler Temperature
bt
HL
High Limit
HL
err
Error Code
Err
f
Degrees Fahrenheit
°F
c
Degrees Celsius
°C
OPerATiNg THe BOiLer - SYSTeM STArT-UP
Figure 22 - Aquastat