background image

Communication 

TCD Electronics | Function Manual | Version: TCD_PROFI_S_EN_200326_E003 

12 

3.6.

 

Installation check 

 

Make  sure the installation  guidelines provided  by the "Wiring  & Installation  Application 
Guide" on Profibus  Installation  guide  (

http://www.profibus.com/download/installation- 

guide/

are followed.

 

 

Make  sure the wiring  requirements for the device  are met. 

 

Make  sure all connectors  are properly  tightened. 

3.7.

 

Cyclic services 

Below  is  an  overview  of  which  cyclic  services  and  parameter  update  time  the  device  provides.  Input 
(Master view) is defined as values from the flowmeter to the master. Output (Master view) is defined as 
values  from  the  master  to  the  flowmeter.  Update  time  is  the  interval  the  flowmeter  updates  the 
parameters. 

 

Parameter  name 

Update  time

 

Input  
(Master  view) 

Mass  flow 

10 msec 

Density 

10 msec 

Medium temperature 

30 msec 

Totalizer  1 (single  and  double  precision 

10 msec 

Totalizer 2 (single and double precision) 

30 msec 

Fractional  flow A 

10 msec 

Fractional  flow B 

30 msec 

Fractional  flow  % A 

30 msec 

Fractional  flow  % B 

30 msec 

Standard  volume  flow 

10 msec 

Frame  temperature 

30 msec 

Totalizer  3 (single  and  double  precision) 

30 msec 

Control status: 

 

Zero point adjustment  active 

 

Outputs forced 

 

Process  values  frozen 

10 msec 

Dosing: 

 

Zero point adjustment  active 

 

Dosing  status 

 

Dosing  output (analogue/discrete) 

30 msec 

Output  
(Master  view) 

Dosing  control: 

 

Start 

 

Stop 

 

Pause 

 

Resume 

 

Clean 

Start zero point adjustment 
Force / unforce  outputs 
Control totalizer 1 
Control totalizer 2 
Control totalizer 3 

Tab. 1: Cyclic services  

 

Содержание PRO Series

Страница 1: ...PRO Series Function Manual TRICOR Coriolis Mass Flow Meter TCD 9x00 Profibus ...

Страница 2: ...EN_200326_E003 2 Manual Version TCD_PROFI_S_EN_200326_E003 This document is supplied as standard in electronic media with the device Latest version can be downloaded at www tricorflow com NOTE This manual applies to the Coriolis Flow Meter with the brand TRICOR ...

Страница 3: ...Analog Input block Mass flow 18 3 8 3 Slot 1 Transducer Block 19 3 8 4 Slot 2 Analog Input block Density 29 3 8 5 Slot 3 Analog Input block Medium temperature 30 3 8 6 Slot 4 Totalizer block 1 30 3 8 7 Slot 5 Totalizer block 2 33 3 8 8 Slot 6 Analog Input block Volume flow 36 3 8 9 Slot 7 Analog Input block Fractional flow A block 36 3 8 10 Slot 8 Analog Input block Fractional flow B block 37 3 8 ...

Страница 4: ...al Version TCD_PROFI_S_EN_200326_E003 4 3 9 Access Control 46 3 10 Alarm error an system messages 47 3 10 1 Introduction 47 3 10 2 Diagnosis Response 47 4 CABLE SPECIFICATIONS 49 5 LISTINGS 50 5 1 List of Figures 50 5 2 List of Tables 50 ...

Страница 5: ...if proper precautions are not taken WARNING indicates that death or severe personal injury may result if proper precautions are not taken CAUTION indicates that minor personal injury can result if proper precautions are not taken NOTE indicates that property damage can result if proper precautions are not taken If more than one degree of danger is present the warning notice representing the highes...

Страница 6: ...ssembly commissioning operation and maintenance are required to ensure that the products operate safely and without any problems The permissible ambient conditions must be complied with The information in the relevant documentation must be observed 1 4 Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described Since vari...

Страница 7: ...d for more detailed information you need the product specific manual Availablefor download from Flow documentation www tricorflow com This manual applies to the TRICOR TCD 9x00 transmitter Profibus DP PA version only The TCD 9x00 transmitter is intended to be used for TCMP and TCMQ series In order to operate a Coriolis flow meter you also need Operating Instructions See Flow documentation www tric...

Страница 8: ...nstallation in hazardous area The PROFIBUS DP module is not allowed for use in hazardous areas The PROFIBUS PA module is allowed for use in hazardous areas 3 3 Profibus The transmitter has a modular design with discrete replaceable electronic modules and connection boards to maintain separation between functions and facilitate field service All modules are fully traceable and their provenance is i...

Страница 9: ...play HMI Terminal space HMI data cable Power supply terminal protection cover SD card Housing cover DIP switch for custody transfer Wiring tool DIP switch for HART and Modbus I O cassette optional HMI port I O configuration keys optional USB service port M12 socket version dependent for TCD 9200 Transmitter cassette Sensor module Power supply module Cover lock Cable entry ...

Страница 10: ...vice from power 2 Unscrew the locking screw of the display and remove the display lid using a wrench bar if necessary 3 Carefully remove display and cable plug NOTE Use a screwdriver to release the display as shown in photo below The display is held in place with three clips 4 Remove the screw holding the transmitter cassette Pull out the transmitter cassette 5 Changing termination at the transmit...

Страница 11: ... 3 5 Connecting the Profibus CH1 WARNING Warnings provide very important information for the correct usage of the equipment Not observing the warnings may lead to danger for the equipment and to danger for health and life of the user 1 Remove cap and ferrule from cable gland and slide onto cable 2 Push cable through open gland and cable path 3 Restore ferrule and tighten cap to lightly hold cable ...

Страница 12: ...ter Update time is the interval the flowmeter updates the parameters Parameter name Update time Input Master view Mass flow 10 msec Density 10 msec Medium temperature 30 msec Totalizer 1 single and double precision 10 msec Totalizer 2 single and double precision 30 msec Fractional flow A 10 msec Fractional flow B 30 msec Fractional flow A 30 msec Fractional flow B 30 msec Standard volume flow 10 m...

Страница 13: ...ock Manufacturer Specific 10 16 37 Fraction Flow B block Manufacturer Specific 11 16 37 Analog input block Standard volume flow 12 16 37 Analog input block Frame temperature 13 16 32 Totalizer block 3 14 16 19 Binary commands Manufacturer Specific 15 16 33 Dosing block Manufacturer Specific 30 255 Used for direct access of MODBUS registers Tab 2 Acyclic data 3 8 1 Slot 0 Physical Block Index Param...

Страница 14: ...d start application reset Bit 5 maintenance required Bits 6 7 reserved Byte 2 Bit 0 maintenance alarm Bit 1 maintenance demanded Bit 2 function check Bit 3 invalid process conditions Bit 4 update event Bits 5 7 reserved Byte 3 Bits 0 6 reserved Bit 7 more information is available 31 IM_Tag_Location Vsible String 22 Read Write Device location 32 IM_Revision_ Counter Unsigned16 Read only The device ...

Страница 15: ...cation Reset and Communication Reset 36 IM_DESCRIPTOR Visible String 54 Read Write 54 character long description field 37 LANGUAGE Visible String 2 Read Language setting of the local user interface The coding is according Alpha 2 of ISO639 Available codes en Englisch fr French de German es Spanish it Italian zh Chinese 39 STARTUP_PAR AM VALIDITY Unsigned8 Read only Provides information if the cycl...

Страница 16: ...in quality codes and the DIAGNOSIS parameter in case that manual acknowledge mode is enabled UPDATE_EVENT_MODE 47 UP DATE EVENT MODE Unsigned8 Read Write Holds the configuration for the behavior of the update event flag in all status bytes 0 auto acknowledge after 20 seconds 1 manual acknowledge by means of parameter UP DATE_EVENT_ACK 48 BUS_ADDRESS Octet String 6 Read only Detailed information of...

Страница 17: ...ssible all with one read and or write request to PARAMS_1_DATA 63 PARAMS_1_ DATA Read Write 64 byte data field for parameters specified by PAR AMS_1_REGISTER 64 PARAMS_2_ REGISTER Read Write 64 bytes to define 32 MODBUS registers that are accessible all with one read and or write request to PARAMS_2_DATA 65 PARAMS_2_ DATA Read Write 128 byte data field for parameters specified by PAR AMS_2_REGISTE...

Страница 18: ...s flow Index Parameter name Data type size Access Annotation 16 BLOCK_OBJECT DS 32 Read only Constant block information 17 CURRENT_MODE Unsigned8 Read only 8 Automatic 128 Out of service 22 PROCESS_VALUE DS 101 Read only Process value with quality code 23 PROCESS_VALUE UNITS Unsigned16 Read only Read only copy of the transducer block unit setting 24 DAMPING Float32 Read Write Low pass filter of th...

Страница 19: ... UNITS Unsigned16 Read Volume flow units The coding is according the PROFIBUS PA Profile specification 1347 m s 1348 m min 1349 m h 1350 m d 1351 l s 1352 l min 1353 l h 1354 l d 1355 Ml d 1356 ft s 1357 ft min 1358 ft h 1359 ft d 1362 gal s 1363 gal min 1364 gal h 1365 gal d 1366 Mgal d 1367 i gal s 1368 i gal min 1369 i gal h 1370 i gal d 1371 BBL s 1372 BBL min 1373 BBL h 1374 BBL d 1448 µgal s...

Страница 20: ...i gal min 1471 µi gal h 1472 mi gal h 1473 ki gal h 1474 Mi gal h 1475 µi gal d 1476 mi gal d 1477 ki gal d 1478 Mi gal d 1479 µBBL s 1480 mBBL s 1481 kBBL s 1482 MBBL s 1483 µBBL min 1484 mBBL min 1485 kBBL min 1486 MBBL min 1487 µBBL h D1942 1488 mBBL h 1489 kBBL h 1490 MBBL h 1491 µBBL d 1492 mBBL d 1493 kBBL d 1494 MBBL d 1495 µm s 1496 mm s 1497 km s 1498 Mm s 1499 µm min 1500 mm min 1501 km ...

Страница 21: ... s 1581 af min 1582 af h 1583 af d 1584 fl oz US s 1585 fl oz US min 1586 fl oz US h 1587 fl oz US d 1633 hl s 1634 hl min 1635 hl h 1636 hl d 1637 BBL s 1638 BBL min 1639 BBL h 1640 BBL d 1642 BBL s 1643 BBL min 1644 BBL h 1645 BBL d 1995 customized unit 32768 bush s 32769 bush min 32770 bush h 32771 bush d 32772 yd s 32773 yd min 32774 yd h 32775 yd d 32776 in s 32777 in min 32778 in h 32779 in ...

Страница 22: ... kg s 1323 kg min 1324 kg h 1325 kg d 1326 t s 1327 t min 1328 t h 1329 t d 1330 lb s 1331 lb min 1332 lb h 1333 lb d 1334 STon s 1335 STon min 1336 STon h 1337 STon d 1338 T s 1339 T min 1340 T h 1341 T d 1606 oz s 1607 oz min 1608 oz h 1609 oz d 1995 customized unit 80 MASS_FLOW_LO_L IMIT Float32 Read only Mass flow low limit 81 MASS_FLOW_HI_LI MIT Float32 Read only Mass flow high limit 82 DENSI...

Страница 23: ...perature unit that is used by temperature values Coding 1000 K 1001 C 1002 F 1003 R 88 TEMPERATURE _LO_LIMIT Float32 Read only Media temperature flow low limit 89 TEMPERATURE _HI_LIMIT Float32 Read only Media temperature high limit 98 LOW_FLOW_CUT_ OFF Float32 Read Write Mass flow low flow cut off filter 99 FLOW_DIREC TION Unsigned8 Read Write Assigns an arbitrary positive or negative sign to the ...

Страница 24: ...TY_UNITS TEMPERATURE_UNITS LOW_FLOW_CUTOFF FLOW_DIRECTION LINK_NE107_CORIOLIS 123 FRAME_TEMPE RATURE 101 Read only Process value in TEMPERATURE_UNITS 124 STANDARD_VOL UME FLOW 101 Read only Process value in STANDARD_VOLUME_FLOW_UNITS 125 STANDARD_VOL UME FLOW UNITS Unsigned16 Read Write Standard volume flow unit The coding is according the PROFIBUS PA Profile specification 126 FRACTION_FLOW_ A 101...

Страница 25: ...rofile specification 1318 g s 1319 g min 1320 g h 1321 g d 1322 kg s 1323 kg min 1324 kg h 1325 kg d 1326 t s 1327 t min 1328 t h 1329 t d 1330 lb s 1331 lb min 1332 lb h 1333 lb d 1334 STon s 1335 STon min 1336 STon h 1337 STon d 1338 T s 1339 T min 1340 T h 1341 T d 1606 oz s 1607 oz min 1608 oz h 1609 oz d 1995 customized unit Selected unit for fractional volume flow value that affects values a...

Страница 26: ...1370 i gal d 1371 BBL s 1372 BBL min 1373 BBL h 1374 BBL d 1448 µgal s 1449 mgal s 1450 kgal s 1451 Mgal s 1452 µgal min 1453 mgal min 1454 kgal min 1455 Mgal min 1456 µgal h 1457 mgal h 1458 kgal h 1459 Mgal h 1460 µgal d 1461 mgal d 1462 kgal d 1463 µi gal s 1464 mi gal s 1465 ki gal s 1466 Mi gal s 1467 µi gal min 1468 mi gal min 1469 ki gal min 1470 Mi gal min 1471 µi gal h 1472 mi gal h 1473 ...

Страница 27: ...489 kBBL h 1490 MBBL h 1491 µBBL d 1492 mBBL d 1493 kBBL d 1494 MBBL d 1495 µm s 1496 mm s 1497 km s 1498 Mm s 1499 µm min 1500 mm min 1501 km min 1502 Mm min 1503 µm h 1504 mm h 1505 km h 1506 Mm h 1507 µm d 1508 mm d 1509 km d 1510 Mm d 1511 cm s 1512 cm min 1513 cm h 1514 cm d 1518 kl min 1519 kl h 1520 kl d 1563 ml min 1577 ml s 1578 ml h 1579 ml d 1580 af s 1581 af min 1582 af h 1583 af d 158...

Страница 28: ... Mft d 129 FRACTION FLOW PCT A 101 Read only Percentage fraction process value 130 FRACTION FLOW PCT B 101 Read only Percentage fraction process value 131 FRACTION FLOW PCT UNITS Unsignd16 Read Write Unit code that affects FRACTION_FLOW_PCT_A and FRACTION_FLOW_PCT_B Coding 1342 1428 proof 132 LOW_VOLUME FLOW CUT OFF Float32 Read Write Low flow cut off filter setting for volume flow 133 CUSTOM_UNIT...

Страница 29: ...lot 1 Transducer Block 3 8 4 Slot 2 Analog Input block Density Index Parameter name Data type size Access Annotation 16 BLOCK_OBJECT DS 32 Read only Constant block information 17 CURRENT_MODE Unsigned8 Read only Follows the target mode of the Physical Block 8 Automatic 128 Out of service 22 PROCESS_VALUE DS 101 Read only Process value with quality code 23 PROCESS_VALUE UNITS Unsigned16 Read only R...

Страница 30: ...VAUE parameter including the quality code This could be used to verify the PLC program behavior 26 VIEW_1 Read only Read only parameter to read CURRENT_MODE MEDIUM TEMPERATURE MEDIUM TEMPERATURE UNITS DAMPING SIMULATE Manufacturer Specific 36 PROCESS_VALUE UNITS TEXT Visible String 8 Read only Tab 7 Slot 3 Analog Input block Medium temperature 3 8 6 Slot 4 Totalizer block 1 Index Parameter name Da...

Страница 31: ...INPUT_SELECTOR is set to mass flow the TOTAL_UNITS only accepts mass units Available Mass units 1088 kg 1089 g 1090 mg 1091 Mg 1092 t 1093 oz 1094 lb 1095 STon 1096 T 1567 ct 1568 lb tr 1569 oz tr 1995 customized unit Available Volume units 1034 m 1035 dm 1036 cm 1037 mm 1038 l 1039 cl 1040 ml 1041 hl 1042 in 1043 ft 1044 yd 1045 mile 1048 gal 1046 pint 1047 quart 1049 i gal 1050 bush 1051 BBL 105...

Страница 32: ...stopped during occurrence of BAD status of incoming values 2 MEMORY totalization is continued based on the last incoming value with GOOD status before the first occurrence of BAD status 27 PRESET_TOT Float32 Read Write This 32 bit floating point value is used as a preset for the internal value of the FB algorithm The value gets effective if using the SET function This value follows TOTAL_UNITS 28 ...

Страница 33: ...ck information used to identify the block type 17 CURRENT_MODE Unsigned8 Read only Set to Out of service if the TARGET_MODE parameter of the Physical Block is set to Out of service Available modes 8 Automatic 128 Out of service 22 TOTAL 101 Read only 32 bit floating point process value with quality code The value follows TOTAL_UNITS TOTAL and TOTAL_DOUBLE are always on pair i e both showing the sa...

Страница 34: ...liq 1517 kl 1570 fl oz US 1572 af 1641 BBL fed 1995 customized unit Available Standard volume units 1053 Sft 1573 Nm 1574 Nl 1575 Sm 1576 Sl 1995 customized unit 24 SET_TOT Unsigned8 Read Write 1 RESET assign value 0 to Totalizer 2 PRESET assign value of PRESET_TOT to Totalizer 3 HOLD totalization stopped 4 TOTALIZE normal operation of the Totalizer 25 MODE_TOT Unsigned8 Read Write 0 FORWARD AND B...

Страница 35: ... 28 INPUT_SELECTOR Unsigned8 Read Write 1 Volume flow 2 Standard volume flow 3 127 reserved 128 Fraction Flow A 129 Fraction Flow B 29 SIMULATE DS 50 Read Write Simulation 30 TOTAL_DOUBLE 106 Read only 64 bit floating point process value with quality code The value follows TOTAL_UNITS TOTAL and TOTAL_DOUBLE are always on pair i e both showing the same totalized value but with a different precision...

Страница 36: ...OCESS_VALUE parameter in cluding the quality code This could be used to verify the PLC program behavior 27 VIEW_1 Read only Read only parameter to read CURRENT_MODE VOLUME FLOW VOLUME FLOW UNITS DAMPING SIMULATE Manufacturer Specific 37 PROCESS_VALUE UNITS TEXT Visible Strng 8 Read only Tab 10 Slot 6 Analog Input block Volume flow 3 8 9 Slot 7 Analog Input block Fractional flow A block Index Param...

Страница 37: ...notation 16 BLOCK_OBJECT DS 32 Read only Constant block information 17 CURRENT_MODE Unsigned8 Read only Follows the target mode of the Physical Block 8 Automatic 128 Out of service 22 PROCESS_VALUE DS 101 Read only Process value with quality code 23 PROCESS_VALUE UNITS Unsigned16 Read only Read only copy of the transducer block unit setting 24 DAMPING Float32 Read Write Low pass filter of the inpu...

Страница 38: ...VALUE parameter in cluding the quality code This could be used to verify the PLC program behavior 27 VIEW_1 Read only Read only parameter to read CURRENT_MODE FRACTIONAL FLOW A FRACTIONAL FLOW A UNITS DAMPING SIMULATE Manufacturer Specific 37 PROCESS_VALUE UNITS TEXT Visible Strng 8 Read only Tab 13 Slot 9 Analog Input block Fractional flow A block 3 8 12 Slot 10 Analog Input block Fractional flow...

Страница 39: ...tion 16 BLOCK_OBJECT DS 32 Read only Constant block information 17 CURRENT_MODE Unsigned8 Read only Follows the target mode of the Physical Block 8 Automatic 128 Out of service 22 PROCESS_VALUE DS 101 Read only Process value with quality code 23 PROCESS_VALUE UNITS Unsigned16 Read only Read only copy of the transducer block unit setting 24 DAMPING Float32 Read Write Low pass filter of the input va...

Страница 40: ...SS_VALUE parameter in cluding the quality code This could be used to verify the PLC program behavior 27 VIEW_1 Read only Read only parameter to read CURRENT_MODE FRAME TEMPERATURE FRAME TEMPERATURE UNITS DAMPING SIMULATE Manufacturer Specific 37 PROCESS_VALUE UNITS TEXT Visible Strng 8 Read only Tab 16 Slot 12 Analog Input block Frame temperature 3 8 15 Slot 12 Analog Input block Frame temperature...

Страница 41: ...size Access Annotation 16 BLOCK_OBJECT DS 32 Read only Constant block information 17 CURRENT_MODE Unsigned8 Read only Set to Out of service if the TARGET_MODE parameter of the Physical Block is set to Out of service Available modes 8 Automatic 128 Out of service 22 PROCESS_VALUE 101 Read only 32 bit floating point process value with quality code The value follows TOTAL_UNITS TOTAL and TOTAL_DOUBLE...

Страница 42: ...cl 1040 ml 1041 hl 1042 in 1043 ft 1044 yd 1045 mile 1048 gal 1046 pint 1047 quart 1049 i gal 1050 bush 1051 BBL 1052 BBL liq 1517 kl 1570 fl oz US 1572 af 1641 BBL fed 1995 customized unit Available Standard volume units 1053 Sft 1573 Nm 1574 Nl 1575 Sm 1576 Sl 1995 customized unit 24 SET_TOT Unsigned8 Read Write 1 RESET assign value 0 to Totalizer 2 PRESET assign value of PRESET_TOT to Totalizer...

Страница 43: ...Float32 Read Write This 32 bit floating point value is used as a preset for the internal value of the FB algorithm The value gets effective if using the SET function This value follows TOTAL_UNITS 28 INPUT_SELECTOR Unsigned8 Read Write 0 Mass flow 1 Volume flow 2 Standard volume flow 3 127 reserved 128 Fraction Flow A 129 Fraction Flow B 130 255 reserved 29 SIMULATE DS 50 Read Write 30 TOTAL_DOUBL...

Страница 44: ...ent Bit 1 Freeze process values Bit 2 Force outputs Byte 1 Command Validity Mask Bit coded information to indicate which bit or bits are valid to be processed by the device Bit 0 process Start zero point adjustment com mand Bit 1 process Freeze process values command Bit 2 process Force outputs command The command bit is only processed if the corresponding mask bit is set Otherwise the com mand in...

Страница 45: ...Volume Flow 4 Standard Volume Flow 5 Fraction Flow Media A 6 Fraction Flow Media B 22 AMOUNT_DONE DS 101 Read only Current amount that is totalized since the start of the batch cycle Includes a quality code 23 AMOUNT_RE MAINING DS 101 Read only Amount that is missing to complete the current batch 24 RECIPE_ID Unsigned8 Read Write Active recipe that specifies the used parameter set Valid range 1 5 ...

Страница 46: ...ROFIBUS connection If the access level of the acyclic PROFIBUS connection is smaller than the protection level of the parameter that is desired to be modified then the attempt to modify the parameter is rejected by the device The following access levels are provided Access level Description READ ONLY Having this access level the acyclic PROFIBUS master is not able to modify the device configuratio...

Страница 47: ...set Maintenance required Maintenance alarm Maintenance demanded Function check Out of specification Parameter update Extension available NE107 diagnostic 14 19 General faults and faults conditions Sensor element exciter faulty Error in evaluation electronics Error in internal energy supply Error in sensor element Error in actuator element Faulty installation e g dead space Parameter setting error ...

Страница 48: ...y in electronics area Medium in electronics area Mechanical damage Communication error Foreign material in electro area Detailed alarm status 23 26 ALARM_STATUS_1 27 30 ALARM_STATUS_2 31 34 ALARM_STATUS_3 35 38 ALARM_STATUS_4 39 42 ALARM_STATUS_5 43 46 ALARM_STATUS_6 47 50 ALARM_STATUS_7 51 54 ALARM_STATUS_8 55 58 ALARM_STATUS_9 59 62 ALARM_STATUS_10 Tab 21 Diagnosis Response ...

Страница 49: ...3 dB km Capacitive asymmetry 2 nF km Envelope delay distortion 7 9 to 39 kHz 1 7 μs km Shield coverage 90 Max cable length inc spurs 1 m 1900 m 6233 ft Tab 22 Cable type A specifications Overall cable length The overall cable length is made up of the length of the main cable and the length of all spurs 1 m 3 28 ft The maximum network expansion depends on the type of ignition protection and the cab...

Страница 50: ... 9 Slot 5 Totalizer block 2 35 Tab 10 Slot 6 Analog Input block Volume flow 36 Tab 11 Slot 7 Analog Input block Fractional flow A block 37 Tab 12 Slot 8 Analog Input block Fractional flow B block 37 Tab 13 Slot 9 Analog Input block Fractional flow A block 38 Tab 14 Slot 10 Analog Input block Fractional flow B block 39 Tab 15 Slot 11 Analog Input block Standard volume flow 39 Tab 16 Slot 12 Analog ...

Страница 51: ...echanik GmbH Liebigstraße 5 85757 Karlsfeld Germany 49 8131 59391 100 sales kem kueppers com www kem kueppers com ASIA PACIFIC MIDDLE EAST KEM Küppers Elektromechanik GmbH 73 Science Park Drive 01 08 09 Cintech 1 Singapore 118254 65 6347 6162 singapore kem kueppers com www kem kueppers cn CHINA KEM flow technology Beijing Co Ltd Rm 906 Block C Ruipu Office Bldg No 15 HongJunYingNan Road Chaoyang D...

Отзывы: