Communication
TCD Electronics | Function Manual | Version: TCD_PROFI_S_EN_200326_E003
30
3.8.5.
Slot 3: Analog Input block
–
Medium temperature
Index Parameter name
Data type
[size]
Access Annotation
16
BLOCK_OBJECT
DS-32
Read
only
Constant block information
17
CURRENT_MODE
Unsigned8
Read
only
Follows the target mode of the Physical Block
8: Automatic
128: Out of service
22
PROCESS_VALUE
DS-101
Read
only
Process value with quality code
23
PROCESS_VALUE
UNITS
Unsigned16 Read
only
Read-only copy of the transducer block unit setting
24
DAMPING
Float32
Read
Write
Low-pass filter of the input value. Value in seconds.
Valid range: 0…100 s
25
SIMULATE
DS-50
Read
Write
Possibility to simulate the PROCESS_VAUE parameter
(including the quality code). This could be used to
verify the PLC program behavior.
26
VIEW_1
Read
only
Read-only parameter to read
•
CURRENT_MODE
•
MEDIUM TEMPERATURE
•
MEDIUM TEMPERATURE UNITS
•
DAMPING
•
SIMULATE
Manufacturer Specific
36
PROCESS_VALUE
UNITS TEXT
Visible
String(8)
Read
only
Tab. 7: Slot 3: Analog Input block
–
Medium temperature
3.8.6.
Slot 4: Totalizer block 1
Index Parameter name
Data type
[size]
Access Annotation
16
BLOCK_OBJECT
DS-32
Read
only
Constant block information
17
CURRENT_MODE
Unsigned8
Read
only
Set to “Out of service” if the TARGET_MODE
parameter of the Physical
Block is set to “Out of service”.
Available modes:
8: Automatic
128: Out of Service
22
TOTAL
101
Read
only
32-bit floating point process value with quality code.
The value follows TOTAL_UNITS.
TOTAL and TOTAL_DOUBLE are always “on pair” i.e.
both showing the same totalized value but with a
different precision.