Communication
TCD Electronics | Function Manual | Version: TCD_PROFI_S_EN_200326_E003
16
Index Parameter name
Data type
[size]
Access Annotation
43
BAUD RATE
Unsigned8
Read
only
Shows the current used baud rate.
0: 9.6 kbit/s
1: 19.2 kbit/s
2: 93.75 kbit/s
3: 187.5 kbit/s
4: 500 kbit/s
5: 1.5 Mbit/s
6: 3 Mbit/s
7: 6 Mbit/s
8: 12 Mbit/s
9: 31.25 kbit/s (MBP)
Note: The PA variant returns always code 9. The DP
variant does not support code 9 (31.25 kbit/s)
44
WRITE_PRO-
TECTION
Unsigned16 Read
only
Information about active parameter protection.
Bit 2: Password write protection enabled
Bit 15: Custody transfer mode enabled
45
ALARM_DELAY
Unsigned16 Read
Write
A coming event is suppressed until the suppression
time has elapsed. This prevents alarm flooding.
46
UP-
DATE_EVENT_ACK
Unsigned8
Read
Write
Command to reset the update event flag in quality
codes and the DIAGNOSIS parameter in case that
manual acknowledge mode is enabled
(UPDATE_EVENT_MODE)
47
UP-
DATE EVENT
MODE
Unsigned8
Read
Write
Holds the configuration for the behavior of the
update event flag in all status bytes
0: auto-acknowledge after 20 seconds.
1: manual acknowledge by means of parameter
UP‐
DATE_EVENT_ACK
48
BUS_ADDRESS
Octet-
String(6)
Read
only
Detailed information of the device, bitwise coded.
Allows setting of diagnostic flags specified by the
NAMUR recommendation NE107 comprising
common device diagnostics. The device type specific
diagnostics are allocated to the respective
transducer block (module/submodule) that
characterizes the device type mainly.
49
LINK_NE107_
COMMON
DS-69
Read
Write
Indicates / controls the reaction of the device on
device specific diagnostic events.
50
View_1
Read
only
Parameter to read the following block parameters at
once:
•
BLOCK_OBJECT
•
OrderID
•
SOFTWARE_REVISION
•
HARDWARE_REVISION
•
VendorID
•
DeviceID
•
IM_Serial_Number
•
IM_Profile_ID
•
IM_Profile_Specific_Type