Communication
TCD Electronics | Function Manual | Version: TCD_PROFI_S_EN_200326_E003
17
Index Parameter name
Data type
[size]
Access Annotation
51
View_2
Read
Write
Parameter to read the following block parameters at
once:
•
CURRENT_MODE
•
DIAGNOSIS
•
IM_Revision_Counter
•
STARTUP_PARAM_VALIDITY
•
BUS_ADDRESS
•
IDENT_NUMBER
•
BAUD_RATE
•
WRITE_PROTECTION
•
NE107_COMMON
52
View_3
Read
Write
Parameter to read and write the following block
parameters at once:
•
IM_Tag_Function
•
IM_Tag_Location
•
IM_Descriptor
•
LANGUAGE
•
IM_Date
•
IDENT_NUMBER_SELECTOR
53
View_4
Read
Write
Parameter to read and write the following block
parameters at once:
•
TARGET_MODE
•
ALARM_DELAY
•
UPDATE_EVENT_MODE
•
LINK_NE107_COMMON
62
PARAMS_1_
REGISTER
Read
Write
32 bytes to define 16 MODBUS registers that are
accessible all with one read and/or write request to
PARAMS_1_DATA
63
PARAMS_1_
DATA
Read
Write
64 byte data field for parameters specified by
PAR‐
AMS_1_REGISTER
64
PARAMS_2_
REGISTER
Read
Write
64 bytes to define 32 MODBUS registers that are
accessible all with one read and/or write request to
PARAMS_2_DATA
65
PARAMS_2_
DATA
Read
Write
128 byte data field for parameters specified by
PAR‐
AMS_2_REGISTER
This parameter is intentionally the double size of
PAR‐
AMS_1_DATA. Some PROFIBUS components
might still have a frame length limit that does not
allow the access of larger data units. For these
components PARAMS_1_DATA can be used.
68
LIST_IDENT_
NUM_SUP
Unsigned16 Read
only
Provides information which ident numbers are
supported by the device. This includes the profile
GSD files.
69
CURRENT_AC-
SESS LEVEL
Unsigned8
Read
only
Current access level of the acyclic connection. The
access level is handled for each acyclic connection.
2: Read only
3: User
4: Expert