Communication
TCD Electronics | Function Manual | Version: TCD_PROFI_S_EN_200326_E003
15
Index Parameter name
Data type
[size]
Access Annotation
35
RESET
Unsigned16 Read
Write
Valid Codes:
1: Application Reset:
Is the command for resetting a device to
Profile default values. The setting of the bus
address is not affected.
2506: Restart
is the command for a restart of the device. All
non-volatile parameters re-main unchanged;
all dynamic parameters are reset to their
defaults.
2712: Communication Reset
The bus address is set to its default address;
other parameterization remains unchanged.
The bus address is changed immediately
regardless if the device is in cyclic data transfer
state. The reset is not suspended up to a
subsequent power cycle / warm start. The
No_Add_Chg_Flag corresponding to the
Set_Slave_Add service is cleared.
2713: Application and Communication Reset
Combined Application Reset and
Communication Reset
36
IM_DESCRIPTOR
Visible-
String(54)
Read
Write
54 character long description field
37
LANGUAGE
Visible-
String(2)
Read
Language setting of the local user interface. The
coding is according Alpha-2 of ISO639. Available
codes:
“en”
Englisch
“
fr
”
French
“
de
”
German
“
es
”
Spanish
“
it
”
Italian
“zh”
Chinese
39
STARTUP_PAR-AM
VALIDITY
Unsigned8
Read
only
Provides information if the cyclic master has sent
startup parameters that has been declared as valid
to be taken to adjust the device parameterization.
40
IDENT_NUMBER
SELECTOR
Unsigned8
Read
only
Specifies which ident number is used
0: PA profile 4 specific ident number
0 : PA profile 4 specific ident number
1 : Device specific ident number (81CB/81CC)
127: Automatic adaption (default)
129: PA profile 3 specific (9700, 1 AI)
130: PA profile 3 specific (9701, 2 AI)
131: PA profile 3 specific (9702, 3 AI)
132: PA profile 3 specific (9742, 3 AI, 1 TOT)
41
BUS_ADDRESS
Unsigned8
Read
Write
PROFIBUS slave address that is currently set. Used by
the parameterization tool to create a complete
snapshot of the device parameterization.