Communication
TCD Electronics | Function Manual | Version: TCD_PROFI_S_EN_200326_E003
18
Index Parameter name
Data type
[size]
Access Annotation
70
DEFAULT_AC-
SESS LEVEL
Unsigned8
Read
Write
Initial access level for an acyclic connection. See also
access control
2: Read only
3: User
71
LOGIN_USER
Unsigned16 Read
Write
Input of the end user PIN to change the current
AC‐
CESS_LEVEL of the acyclic connection.
Reading this parameter indicates if user privilege is
granted (1) or not (0).
72
LOGIN_EXPERT
Unsigned16 Read
Write
Input of the service user PIN to change the current
AC‐
CESS_LEVEL of the acyclic connection
Reading this parameter indicates if user privilege is
granted (1) or not (0).
Tab. 3: Slot 0, Physical Block
3.8.2.
Slot 1: Analog Input block
–
Mass flow
Index Parameter name
Data type
[size]
Access Annotation
16
BLOCK_OBJECT
DS-32
Read
only
Constant block information
17
CURRENT_MODE
Unsigned8
Read
only
8: Automatic
128: Out of service
22
PROCESS_VALUE
DS-101
Read
only
Process value with quality code
23
PROCESS_VALUE
UNITS
Unsigned16 Read
only
Read-only copy of the transducer block unit setting
24
DAMPING
Float32
Read
Write
Low-pass filter of the input value. Value in seconds.
Valid range:
0…100
s
25
SIMULATE
DS-50
Read
Write
Possibility to simulate the PROCESS_VALUE
parameter
(in‐
cluding the quality code). This could
be used to verify the PLC program behavior.
26
INPUT_SELECTOR
Unsigned16 Read
Write
Constant transducer reference information
27
VIEW_1
Read
only
Read-only parameter to read
•
BLOCK_OBJECT
•
CURRENT_MODE
•
PROCESS_VALUE
•
PROCESS_VALUE_UNITS
•
DAMPING
•
SIMULATE
Manufacturer Specific
37
PROCESS_VALUE
UNITS TEXT
Visible-
Strng(8)
Read
only
Tab. 4: Slot 1: Analog Input block
–
Mass flow