9
• Do not install the vent terminal directly over windows or doors.
• The bottom of the vent terminal must be at least 3 feet above any forced air inlet located within 10 feet.
• USA Only: A clearance of at least 4 feet horizontally must be maintained between the vent terminal and gas
meters, electric meters, regulators, and relief equipment. Do not install vent terminal over this equipment. In
Canada, refer to B149.1 Installation Code for clearance to meters, regulators and relief equipment.
• Do not locate the vent terminal under decks or similar structures.
• Top of vent terminal must be at least 5 feet below eves, soffits, or overhangs. Maximum depth of overhang is 3 ft.
• Vent terminal must be at least 6 feet from an inside corner.
• Under certain conditions, water in the flue gas may condense, and possibly freeze, on objects around the terminal
including on the structure itself. If these objects are subject to damage by flue gas condensate, they should be
moved or protected.
• If possible, install the vent and air intake terminals on a wall away from the prevailing wind. Reliable operation of
this boiler cannot be guaranteed if the terminal is subjected to winds in excess of 40 mph.
• Air intake terminal must not terminate in areas that might contain combustion air contaminates, such as near
swimming pools. See Section IV for more information on possible contaminates.
TABLE 6.1: SUMMARY OF HORIZONTAL VENTING OPTIONS
VENT OPTION #
1
3
4
CLASSIFICATION USED IN THIS
MANUAL
HORIZONTAL
TWIN PIPE
HORIZONTAL
TWIN PIPE
HORIZONTAL
CONCENTRIC
ILLUSTRATED IN FIGURE
6.2
6.2
6.3
VENT PIPE STRUCTURE
PENETRATION
WALL
WALL
WALL
AIR INTAKE PIPE STRUCTURE
PENETRATION
WALL
WALL
WALL
VENT PIPE SIZE
4”
5”
100/150mm
CONCENTRIC
AIR INTAKE PIPE SIZE
4”
5”
MAXIMUM
VENT
PIPE
LENGTH
T300
100FT
N.R.
100FT
T399
100FT
T425
100FT
MAXIMUM INT
AKE
PIPE LENGTH
T300
100FT
N.R.
100FT
T399
100FT
T425
100FT
VENT TERMINAL
TRIAD PN
204513
TRIAD PN
240514
TRIAD 230569
CONCENTRIC
TERMINAL
AIR INTAKE TERMINAL
4” 90 ELBOW
5” 90 ELBOW
VENT MATERIAL
APPROVED VENT SYSTEM
SHOWN IN TABLE 6.4
TRIAD
100/150mm
VENT
COMPONENTS
SHOWN IN
TABLE 6.10
AIR INTAKE MATERIAL
GALVANIZED OR PVC
Содержание Triumph series
Страница 2: ......
Страница 31: ...29 FIGURE 6 21b CUTTING VERTICAL TERMINAL FIGURE 6 21c COMPLETING VERTICAL TERMINAL INSTALLATION ...
Страница 34: ...32 FIGURE 6 23 CONDENSATE PIPING ARRANGEMENT ...
Страница 48: ...46 Figure 8 14 Multiple Boiler Piping ...
Страница 50: ...Figure 9 1 Wiring Connections Diagram 48 ...
Страница 51: ...Figure 9 2 Ladder Diagram 49 ...
Страница 69: ...67 PAGE INTENTIONALLY LEFT BLANK ...
Страница 71: ...69 ...
Страница 72: ...70 ...
Страница 73: ...71 ...
Страница 75: ...73 ...
Страница 76: ...74 ...
Страница 78: ...76 ...
Страница 79: ...77 ...
Страница 82: ...80 ...
Страница 83: ...81 155 156 158 157 160 159 ...
Страница 84: ...82 161 162 164 163 166 165 ...
Страница 85: ...83 167 ...