PAR
NO.
DESCRIPTION
PURPOSE
1
T3set DHW
Factory set to 134°F. This value plus 46°F equals the target supply water temperature when
the boiler responds to a call from the indirect water heater thermostat. With 134°F factory
setting, target supply temperature is 180°F when boiler is responding to a call for DHW.
2
DHW system
Factory set to "ON". Field change not recommended.
3
CH system
Factory set to "ON". Field change not recommended.
4
T1top CH Mode
Maximum target supply water temperature when boiler is responding to a call for central
heating. When the outdoor air sensor is connected, this is the maximum supply water
temperature on the reset curve (see Figure 1.2). Note: Settings higher than 180°F increase the
risk of nuisance safety limit activation (b19 errors). Factory set to 180°F.
5
T1foot CH Mode
When the outdoor sensor is connected, T1foot is the minimum supply water temperature (see
Figure 1.2). Factory set to 100°F.
6
T4 minimum
Outdoor temperature at and below which the boiler will operate at the maximum target supply
water temperature (T1top). See Figure 1.2. Factory set to 0°F.
7
T4 maximum
Outdoor temperature at and above which the boiler will operate at the minimum target supply
water temperature (T1 foot). See Figure 1.2. Factory set to 60°F.
8
T4 frost protection
9
T4 correction
10
Tblocking
11
Booster time
12
Tparallel shift
13/14
Maximum fanspeed CH
15/16
Maximum fanspeed DHW
Maximum fan speed (firing rate) when responding to call for DHW
17/18
Minimum fanspeed
19
Ignition fanspeed
20
CH postpump time
21
DHW postpump time
22
CH modulation hysteresis on
23
CH modulation hysteresis off
24
DHW modulation hysteresis on
25
DHW modulation hysteresis off
26
DHW detection hysteresis on
27
DHW detection hysteresis off
28
CH blocking time
29
DHW blocking time
30
DHW -> CH blocking time
31
Modulate back difference T1 - T2
32
RMCI Address
33
Tplus: Setvalue addition for DHW
34-1
2nd CH-Circuit (1st digit)
34-2
CH Type (2nd digit)
This parameter determines what device initiates a call for heat. The factory setting is "0"
("Room Thermostat" when selected using Gascom). If an AM-4 module is used for external
modulation, this parameter is changed to "2" ("0-10V Analog on AM-4: Capacity" when
using Gascom). When this parameter is set to "2", it ignores any call for heat from a
thermostat connected to the boiler and instead responds to 0-10VDC signal connected to the
AM-4 (also see AM-4 instructions).
35-1
DHW 3-wayvalve or pump
35-2
DHW-type (2nd digit)
36
Manual fanspeed
37-1
PWM-pump level (1st digit)
37-2
PWM-pump level (2nd digit)
38
Tset hold boiler warm
39
Ttop for 2nd CH circuit
40
Tfoot for 2nd CH circuit
41
Thysteresis for 2nd CH circuit
42-1
Pump settings for CH and DHW
42-2
Minimum Off Cycle (2nd digit)
Field Change Not Recommended
Field Change Not Recommended
Field Change Not Recommended
Field Change Not Recommended
Table A.3: Parameter Descriptions
89
Содержание Triumph series
Страница 2: ......
Страница 31: ...29 FIGURE 6 21b CUTTING VERTICAL TERMINAL FIGURE 6 21c COMPLETING VERTICAL TERMINAL INSTALLATION ...
Страница 34: ...32 FIGURE 6 23 CONDENSATE PIPING ARRANGEMENT ...
Страница 48: ...46 Figure 8 14 Multiple Boiler Piping ...
Страница 50: ...Figure 9 1 Wiring Connections Diagram 48 ...
Страница 51: ...Figure 9 2 Ladder Diagram 49 ...
Страница 69: ...67 PAGE INTENTIONALLY LEFT BLANK ...
Страница 71: ...69 ...
Страница 72: ...70 ...
Страница 73: ...71 ...
Страница 75: ...73 ...
Страница 76: ...74 ...
Страница 78: ...76 ...
Страница 79: ...77 ...
Страница 82: ...80 ...
Страница 83: ...81 155 156 158 157 160 159 ...
Страница 84: ...82 161 162 164 163 166 165 ...
Страница 85: ...83 167 ...