8 User Manual
2.2. Electrical system design
Figure 2-3 wiring diagram of the whole TRM inverter system
Please refer to chapter 4 for the detail connecting and install methods.
2.3. The illustration of derating and limit the input power
To avoid inverter to be damaged by over temperature or over current.
Not output power when the temperature of power devices is over 100
℃
or the ambient
temperature is over 75
℃
.
Derate the output power linearly when the temperature of power devices is between 93-100
℃
or
the ambient temperature is between 71-75
℃
.