14 User Manual
Step4:
Insert AC cables through cable gland from outside
;
Step5
:Pull the cables through and fix PE/L1/L2/L3/N cables ends to the terminals according to
markings
:
PE R
S
T
N
PE
L1
L2
L3
N
Figure 4-11
Attention!
Please ensure the corresponding relationship between polarities the core cable and the
hole of the terminal is correct.
Step6
: Screw cap nut tightly onto the cable.
4.3.2. Connection to PV generator (DC input)
Attention!
Safeguard each inverter with an individual manual DC breaker in order that inverter can
be safely disconnected under load when installation & maintenance. The breaker should
have certain capacity of over current and over voltage. In addition, before cutting off the
DC end connection. Please cut off the AC end connection at first.
There are two MPPT trackers (A & B route) provided by the TRM Inverter, and each MPPT tracker
provides 3 DC input interface.
Before connecting PV modules to Trannergy, please make sure the polarity of the DC input
connectors is correct.
DC PANEL OF TRM025KTL/030KTL/033KTL/035KTL
MPPT 1
MPPT 2
Figure 4-12 TRM Series Inverter input interface
Assembly Instruction for Amphenol H4 High Performance Solar Connector