Attention!
The maximum current of each string is less than 12A
;
The maximum open voltage of each string is less than 950V
Attention!
Connectors must not be connected or disconnected under load!
Figure 4-13
Step1
: Assembly Instruction for the male side and female side connector:
Strip cable .276 inches (9/32”) - (7mm) and be careful NOT to nick conductors.
Figure 4-14
Amphenol specified strip tool can be used in this step. Adjust the striper stopper and put the
cable in corresponding notch to strip the length of 7mm. See below figures.
Figure 4-15
Insert striped cable into contact barrel and insure all conductor strands are captured in the contact
barrel and the conductors are visible in the contact barrel observation hole. See below figures.
Figure 4-16