CNT-SVX05A-EN
75
Appendix
Table 62 — (continued) Constant volume space temperature control operation
based on the effective heat/cool output
Note 1:
Heating capacity can be used to control the discharge air temperature to the discharge air setpoint.
Application
mode input
(nviApplicMode)
Heat/cool mode input
(nviHeatCool)
Effective heat
cool mode output
(nvoHeatCool)
Unit Operation
Auto
Not present
Determined by
controller
Fan Enabled
Heating Enabled
Cooling Enabled
Damper Enabled
Heat
Any state
Heat
Fan Enabled
Heating Enabled (Note 1)
Cooling Disabled
Damper Ventilation enabled
Economizer disabled
Morning warm-up
Any state
Morning warm-up
Fan Enabled
Heating Enabled
Cooling Disabled
Damper Closed
Cool
Any state
Cool
Fan Enabled
Heating Disabled (Note 1)
Cooling Enabled
Damper Enabled
Night purge
Any state
Night purge
Fan Enabled
Heating Disabled
Cooling Disabled
Damper Ventilation disabled
Economizer enabled
Pre-cool
Any state
Pre-cool
Fan Enabled
Heating Disabled
Cooling Enabled
Damper Ventilation disabled
Economizer enabled
Off
Any state
Off
Fan Disabled
Heating Disabled
Cooling Disabled
Damper Disabled
Test
Any state
Determined by
controller
Fan Enabled
Heating Enabled
Cooling Enabled
Damper Enabled
Emergency heat
Any state
Determined by
controller
Fan Enabled
Heating Enabled
Cooling Enabled
Damper Enabled
Fan only
Any state
Fan only
Fan Enabled
Heating Disabled
Cooling Disabled
Damper Disabled