Physical specifications
Binary outputs
The binary outputs are normally-open, form A relays. The relays act as a switch,
either making or breaking the circuit between the load (device) and 24VAC. When
binary output 1 is energized, 24VAC is supplied to terminal TB21-1 (OUT),
energizing the supply fan start/stop relay.
Example:
Each binary output has a green status LED on the Tracer
AH.540 control board.
The LED is off when the relay contacts are open. The LED is on when the relay
contacts are closed.
When the binary output relay is off (contact is open), a multimeter should
measure 0VAC across the output terminals. When the binary output relay is on
(contacts are closed), a multimeter should measure 24VAC across the output
terminals.
Table 2 — Binary outputs
Note 1:
Terminals BO 3, BO 4, BO 5, and BO 6 do not serve any function of the Tracer AH.540 controller and are not used.
Description
Function
Factory
Terminals
Field
Terminals
Label
Terminal
Function
Maximum
Output Rating
BO 1
Supply fan
start/stop
J21
TB21-1
TB21-2
OUT
GND
24VAC
Ground
24VA
BO 2
Exhaust fan
start/stop
J22
TB22-1
TB22-2
OUT
GND
24VAC
Ground
24VA
BO 3
Not used
(Note 1)
J23
TB23-1
TB23-2
OUT
GND
Not used
Not used
BO 4
Not used
(Note 1)
J24
TB24-1
TB24-2
OUT
GND
Not used
Not used
BO 5
Not used
(Note 1)
J25
TB25-1
TB25-2
OUT
GND
Not used
Not used
BO 6
Not used
(Note 1)
J26
TB26-1
TB26-2
OUT
GND
Not used
Not used
24VAC
GND
Supply Fan (start/stop)
Relay
Wiring external to the
Termination board
BO 1
TB21-2 (GND)
TB21-1 (OUT)
Termination board