58
CNT-SVX05A-EN
Configuration
Table 38 — Local zone sensor fan switch
Table 39 — Space temperature setpoints
Note 1:
The heating and cooling setpoint high and low limits only apply to the occupied and occupied standby setpoints
and are never applied to the unoccupied setpoints.
Table 40 — Discharge air setpoint limits for constant volume space
temperature control
Note 1:
When the Tracer AH.540 controller is configured for constant volume space temperature control (control mode),
the control algorithm is limited to calculating this high and low discharge air temperature setpoint.
Table 41 — Discharge air temperature control setpoints and setpoint limits
Table 42 — Daytime warm-up
Note 1:
When the space temperature is below the daytime warm-up start setpoint, the daytime warm-up sequence is
initiated.
Note 2:
When the space temperature is above the daytime warm-up stop setpoint, the daytime warm-up sequence is
terminated.
Parameter
Valid range
Default
Local fan switch
Enable or disable
Enable
Default setpoint
Valid range
Default value
Occupied heating setpoint
40 to 115
°
F (4.44 to 46.1°C)
71
°
F (21.7
°
C)
Occupied cooling setpoint
40 to 115
°
F (4.44 to 46.1°C)
74
°
F (23.3
°
C)
Occupied standby heating setpoint
40 to 115
°
F (4.44 to 46.1°C)
67
°
F (19.4
°
C)
Occupied standby cooling setpoint
40 to 115
°
F (4.44 to 46.1°C)
78
°
F (25.6
°
C)
Unoccupied heating setpoint
40 to 115
°
F (4.44 to 46.1°C)
60
°
F (15.6
°
C)
Unoccupied cooling setpoint
40 to 115
°
F (4.44 to 46.1°C)
85
°
F (29.4
°
C)
Heating setpoint low limit (Note 1)
40 to 115
°
F (4.44 to 46.1°C)
40
°
F (4.4
°
C)
Cooling setpoint low limit (Note 1)
40 to 115
°
F (4.44 to 46.1°C)
40
°
F (4.4
°
C)
Heating setpoint high limit (Note 1)
40 to 115
°
F (4.44 to 46.1°C)
104
°
F (40
°
C)
Cooling setpoint high limit (Note 1)
40 to 115
°
F (4.44 to 46.1°C)
104
°
F (40
°
C)
Thumbwheel setpoint
Disable or enable
Enable
Limit
Valid range
Default value
Disharge temperature setpoint high limit (Note 1)
38 to 150
°
F
(3.3 to 65.6
°
C)
104
°
F (40
°
C)
Disharge temperature setpoint low limit (Note 1)
35 to 150
°
F
(1.7 to 65.6
°
C)
45
°
F (7.2
°
C)
Setpoint
Valid range
Default value
Discharge air cooling setpoint
32°F to 86°F
(0°C to 30°C)
55
°
F (12.8
°
C)
Discharge air heating setpoint
50 to 158°F
(10°C to 70°C)
100
°
F (37.8
°
C)
Maximum discharge air cooling setpoint
32°F to 86°F
(0°C to 30°C)
68
°
F (20
°
C)
Minimum discharge air cooling setpoint
32°F to 86°F
(0°C to 30°C)
44.6
°
F (7
°
C)
Maximum discharge air heating setpoint
32°F to 158°F
(0°C to 70°C)
104
°
F (40
°
C)
Minimum discharge air heating setpoint
32°F to 158°F
(0°C to 70°C)
86
°
F (30
°
C)
Parameter
Valid range
Default value
Daytime warm-up start setpoint (Note 1)
40 to 87.0
°
F
(4.4 to 30.6
°
C)
62
°
F (16.7
°
C)
Daytime warm-up stop setpoint (Note 2)
43 to 90
°
F
(6.1 to 32.2
°
C)
71
°
F (21.7
°
C)