76
CNT-SVX05A-EN
Appendix
Table 64 — Constant volume discharge air temperature control and variable air
volume operation based on the effective heat/cool output
Note 1:
Heating capacity can be used to control the discharge air temperature to the discharge air cooling setpoint.
Table 65 — Trane zone sensor module hardwired setpoint adjustment
Application
mode input
(nviApplicMode)
Effective heat
cool mode output
(nvoHeatCool)
Application mode
output
(nvoApplicMode)
Unit Operation
Auto
Determined by
controller
Determined by
controller
Fan Enabled
Heating Enabled
Cooling Enabled
Damper Enabled
Heat
Heat
Heat
Fan Enabled
Heating Enabled
Cooling Disabled
Damper Ventilation enabled
Economizer disabled
Morning warm-up
Morning warm-up
Heat
Fan Enabled
Heating Enabled
Cooling Disabled
Damper Disabled
Cool
Cool
Auto
Fan Enabled
Heating Disabled (Note 1)
Cooling Enabled
Damper Enabled
Night purge
Night purge
Cool
Fan Enabled
Heating Disabled
Cooling Disabled
Damper Ventilation disabled
Economizer enabled
Pre-cool
Pre-cool
Cool
Fan Enabled
Heating Disabled
Cooling Enabled
Damper Ventilation disabled
Economizer enabled
Off
Off
Auto
Fan Disabled
Heating Disabled
Cooling Disabled
Damper Disabled
Test
Determined by
controller
Determined by
controller
Fan Enabled
Heating Enabled
Cooling Enabled
Damper Enabled
Fan only
Fan only
Cool
Fan Enabled
Heating Disabled
Cooling Disabled
Damper Disabled
Maximum flow
heating
Determined by
controller
Determined by
controller
Fan Enabled
Heating Enabled
Cooling Disabled
Damper Enabled
Resistance
setpoint
889.4
Ω
50
°
F
733.6
Ω
58
°
F
577.9
Ω
66
°
F
500.0
Ω
70
°
F
422.1
Ω
74
°
F
344.2
Ω
78
°
F
266.4
Ω
82
°
F
188.5
Ω
86
°
F
110.6
Ω
90
°
F