74
CNT-SVX05A-EN
Appendix
Appendix
Table 63 — Constant volume space temperature control operation based on the
effective heat/cool output
Note 1:
Heating capacity can be used to control the discharge air temperature to the discharge air setpoint.
Application
mode input
(nviApplicMode)
Heat/cool mode input
(nviHeatCool)
Effective heat
cool mode output
(nvoHeatCool)
Unit Operation
Auto
Auto
Determined by
controller
Fan Enabled
Heating Enabled
Cooling Enabled
Damper Enabled
Heat
Heat
Fan Enabled
Heating Enabled
Cooling Disabled
Damper Ventilation enabled
Economizer disabled
Morning warm-up
Morning warm-up
Fan Enabled
Heating Enabled (Note 1)
Cooling Disabled
Damper Closed
Cool
Cool
Fan Enabled
Heating Disabled
Cooling Enabled
Damper Enabled
Night purge
Night purge
Fan Enabled
Heating Disabled
Cooling Disabled
Damper Ventilation disabled
Economizer enabled
Pre-cool
Pre-cool
Fan Enabled
Heating Disabled
Cooling Enabled
Damper Ventilation disabled
Economizer enabled
Off
Off
Fan Disabled
Heating Disabled
Cooling Disabled
Damper Disabled
Test
Determined by
controller
Fan Enabled
Heating Enabled
Cooling Enabled
Damper Enabled
Emergency heat
Determined by
controller
Fan Enabled
Heating Enabled
Cooling Disabled
Damper Enabled
Fan only
Fan only
Fan Enabled
Heating Disabled
Cooling Disabled
Damper Disabled