background image

Installation

SS-SVX004C-EN

11 

grade refrigerant copper piping. Dry nitrogen should be 
flowing through the tubing while soldering at a rate of not 
less than 1-2 CFM. Be careful not to allow solder/piping 
debris to get inside refrigerant lines.
When brazing copper-to-copper connections (piping 
liquid line or suction line), use a phosphorus copper 
brazing alloy with 15% silver. General purpose silver 
brazing alloy with 45% silver is to be used for copper-to-
brass or copper-to steel.

Refrigerant Pipe Sizing

Refrigerant lines for split systems must be sized according 
to the piping distance between the evaporator and the 
condensing unit. Each valve, fitting and bend in the 
refrigerant line must be considered in this calculation. 
Refer to the following chart for standard equivalent 
lengths, in feet, of straight pipe.
The general guidelines in below table may be used to 
assist in determining the size of the refrigerant lines 
between the evaporator section and the remote 
condensing unit.

Table 1.

Standard equivalent ft of straight pipe 

Equivalent Length (ft) of Straight Pipe

OD (in.) 

Line Size

Globe 

Valve

Angle 

Valve

90º 

Elbow

45º 

Elbow

Tee 

Line

Tee 

Branch

1/2

9.0

5.0

0.9

0.4

0.6

2.0

5/8

12.0

6.0

1.0

0.5

0.8

2.5

7/8

15.0

8.0

1.5

0.7

1.0

3.5

1-1/8

22.0

12.0

1.8

0.9

1.5

4.5

1-3/8

28.0

15.0

2.4

1.2

1.8

6.0

1-5/8

35.0

17.0

2.8

1.4

2.0

7.0

2-1/8

45.0

22.0

3.9

1.8

3.0

10.0

2-5/8

51.0

26.0

4.6

2.2

3.5

12.0

3-1/8

65.0

34.0

5.5

2.7

4.5

15.0

3-5/8

80.0

40.0

6.5

3.0

5.0

17.0

Refer to the tables on the following pages for 
recommended suction and liquid line pipe sizes for the 

A/C system that is installed. Things to consider when 
sizing refrigerant piping are the varying BTU capacities of 
indoor evaporators and the equivalent length of pipe 
needed between the remote condensing unit and the 
evaporator. If the pressure drop is too high, the capacity of 
the compressor decreases and the power required 
increases. An excessive refrigerant charge will be used if 
the volume of the piping is too large.

Note:

The size of the equipment pipe connections does 
not indicate the size of the refrigerant lines to be 
used. In cases where the pipe size doesn’t match 
the size of the connection, reducing fittings should 
be used to transition between the connection and 
the pipe.

Suction Line

If the condensing unit is installed above the evaporator, 
the suction line should include a shallow P-trap at the 
lowest point in the piping (see 

Figure 4

). The highest point 

in the suction line should be above the condensing unit 
coil. Additionally, shallow P-traps must be included in the 
suction line for every 20 ft of vertical rise. All horizontal 
refrigerant lines should be pitched in the direction of flow 
at least ¼ inch for every 10 ft.

Note:

All suction lines should be insulated to prevent 
condensation from forming.

Refer to the below figure that shows a typical piping 
diagram for when the condensing unit is located at a 
higher level than the evaporator. In this situation it’s 
important to size the suction line properly. If the suction 
line is sized correctly for full load operation, the velocity of 
the gas may be too low during minimum load conditions 
to carry the refrigerant oil up the suction line to the 
compressor. Decreasing the size of the suction line will 
increase refrigerant velocity however, it will also restrict 
the flow of refrigerant at full load conditions creating an 
excessive refrigerant pressure drop. Ensure the suction 
line is sized to maintain a minimum velocity of 700 fpm of 
refrigerant in horizontal lines and 1500 fpm of refrigerant 
in vertical lines. This will ensure the refrigerant flows at a 
velocity high enough for the refrigerant vapor to carry the 
oil with it to the compressor.

Figure 4.

Piping installation

Pitch in direction of refrigerant flow

Trap in bottom of column

with minimum trap depth possible

Trap every 20 ft (6100 mm) with minimum trap

depth possible

Pitch minimum 1/4 in. for every 10 ft (5 mm/2400 mm)

of run pitch in direction of refrigerant flow

(Suction and Liquid lines) 

Remote

Condensing Unit

Suction Line

Evaporator or

Air Handler

Liquid Line

Содержание TR-OHS RCU Series

Страница 1: ...the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjus...

Страница 2: ...quipment that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Kno...

Страница 3: ...ede these policies Non Trane personnel should always follow local regulations Introduction SS SVX004C EN 3 Copyright This document and the information in it are the property of Trane and may not be us...

Страница 4: ...Procedures 16 Refrigerant Characteristics 19 Settings and Adjustments 20 High Low Pressure Limit Switches 20 Head Pressure Controls 20 Hot Gas Bypass 20 Commissioning and Decommissioning 21 Operation...

Страница 5: ...10 11 Unit RCU Remote Condensing Unit Digit 12 Outdoor Indoor O Outdoor Unit I Indoor Unit About Digits Model numbers are comprised of digits Each digit or set of digits defines the product model Exam...

Страница 6: ...electric box on the RCU O is weatherproof There are several cabinet sizes based on the capacity of the unit Refer to the installation drawing supplied with the unit for the layout and dimensions of th...

Страница 7: ...r located in the electric box The 012 040 model RCU I use a direct drive blower The 042 120 RCU I units have a belt driven blower with separate drive motor Electric Box RCU electrical components are p...

Страница 8: ...provided as standard on RCU O units and as an option on RCU I units A service disconnect switch electrically isolates the unit during routine maintenance The handle of the switch may be locked in the...

Страница 9: ...ly lift unit in a LEVEL position could result in unit dropping and possibly crushing operator technician which could result in death or serious injury and equipment or property only damage Test lift u...

Страница 10: ...ing for ducted systems Refer to the below figure Notes Do not install the A C system directly above electronic equipment that may hinder serviceability Equipment must be level to operate properly Figu...

Страница 11: ...ill be used if the volume of the piping is too large Note The size of the equipment pipe connections does not indicate the size of the refrigerant lines to be used In cases where the pipe size doesn t...

Страница 12: ...of 30 equivalent ft for longer rises individual calculations must be made Sizes assume the use of single risers double risers may be necessary Table 2 Recommended liquid line sizes Recommended Liquid...

Страница 13: ...se and frequency information specified on the system nameplate The supply voltage measured at the unit must be within 10 of the voltage specified on the nameplate refer to the below figure The namepla...

Страница 14: ...the compressor To correct this problem exchange any two of the incoming main power wires at the main power circuit breaker Do not rewire the unit s individual components Electric Box Layout The elect...

Страница 15: ...rform a dry nitrogen leak detection test on the system Using dry nitrogen only pressurize the system to 150 psig Ensure all service and solenoid valves are energized open and that no part of the syste...

Страница 16: ...Failure to follow instructions below could result in death or serious injury Do not work in confined spaces where refrigerant or other hazardous toxic or flammable gas may be leaking Refrigerant or ot...

Страница 17: ...e the cylinder is emptied Initial System Charge Introducing the Refrigerant Charge Follow the steps below to charge systems with R407C refrigerant The initial charge will be performed by introducing l...

Страница 18: ...f refrigerant charge This can be done by using the system controller to enable a call for dehumidification lower the humidity setpoint This process may need to be repeated several times After cycling...

Страница 19: ...Pressure psig R407C 70 55 85 Switch State Opens Closes Low Pressure Switch psig R407C 10 32 High Pressure Switch psig R407C 410 Manual Reset Saturated Refrigerant Pressure Table The refrigerant vapor...

Страница 20: ...liquid flow from the condensing unit to the receiver When using this method of head pressure regulation there must be enough refrigerant in the system to ensure adequate charge at the lowest expected...

Страница 21: ...pressure gas 3 The refrigerant then flows to the condensing unit coil The high temperature high pressure gas from the compressor is cooled and condensed by the flow of air through the condensing unit...

Страница 22: ...he following recommended guidelines When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders fo...

Страница 23: ...care to avoid accidents and ensure proper operation General Maintenance access to the remote condensing unit is through the removable panel on top of the unit Examine the areas around the air inlet an...

Страница 24: ...overload and re set circuit breaker s or motor starter protector s Condensing Unit Head Pressure Too High Non condensable gas or air in system Recover system evacuate per Preparing System for Charging...

Страница 25: ...o the unit Check fan motor starter protector contactor fan cycling switch or fan speed controller Suction Pressure too Low Expansion valve not opening fully indicated by abnormally cold suction line O...

Страница 26: ...ine whether it is an electrical or a mechanical failure An electrical failure will be indicated by the distinct pungent odor once the system has been opened If a burnout has occurred the oil will be b...

Страница 27: ...Cleanup Procedure WARNING Hazardous Voltage Disconnect all electric power including remote disconnects before servicing Follow proper lockout tagout procedures to ensure the power can not be inadverte...

Страница 28: ...r opening the sheave one half turn to decrease speed 7 Replace the sheave key and tighten set screw 8 Proper belt tension is achieved when the belt has a deflection of 1 2 inch per foot of span betwee...

Страница 29: ...Model Number Sales Order Number Item Number Unit Serial Number Description of Problem Obtaining Warranty Parts A support technician will provide troubleshooting assistance over the telephone If it can...

Страница 30: ...gerant charge bubbles in sight glass 2 Check suction and discharge pressure 3 Ensure refrigerant lines are secured 4 Tighten electrical connections 5 Ensure motor mount is secured 6 Clean unit as nece...

Страница 31: ...tolerances Main power wiring connections to the equipment including earth ground have been properly installed Customer supplied main power circuit breaker HACR type or fuses have proper ratings for e...

Страница 32: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Отзывы: