background image

Installation

20

 SS-SVX004C-EN

Settings and Adjustments

High/Low Pressure Limit Switches

RCU units are equipped with hermetically sealed high 
pressure and low-pressure switches. These switches are 
preset by the manufacturer and cannot be adjusted. The 
high pressure switch will open to disengage power to the 
compressor contactor if the discharge pressure rises 
above a specific pressure. The low pressure switch will 
open to disengage power to the compressor contactor if 
suction pressure drops below a specific pressure. The 
system controller should ignore the absence of this signal 
during the cold start delay period after starting of a 
compressor.

R407C Pressure Switch Settings:

The high-pressure switch opens at 410 psig and has a 
manual reset. The low-pressure switch opens at 10 psig

(± 4) and closes at 32 psig (± 5) and has an automatic reset.

Head Pressure Controls

Condensing Unit Fan Cycling

The condensing unit fan cycling switch senses refrigerant 
discharge pressure and turns on the condensing unit fan 
as required to maintain allowable condensing unit 
pressures. This is a high-pressure differential control 
switch with SPST contacts and an automatic reset. The 
switch activates the condensing unit fan contactor, 
cooling the condensing unit to maintain the condensing 
temperature when the discharge pressure rises.

R407C Refrigerant:

Factory setting: The fan cycling switch contacts are set to 
close on a pressure rise to 320 psig and open at 250 psig. 
Set point range is 170 to 375 psig. The differential is set at 
70 psi and is adjustable.

Flooded Head Pressure Control

Flooded head pressure control is designed to maintain 
head pressure during low ambient temperature 
conditions. A head pressure control valve and a receiver is 
provided in the refrigeration circuit to back up liquid 
refrigerant into the condensing unit coil.
When the receiver pressure drops the valve diverts 
discharge gas away from the condensing unit. The liquid 
from the condensing unit is restricted, which allows liquid 
to flow back up in the condensing unit. Flooding the 
condensing unit reduces the area available for heat 
transfer thus raising the condensing pressure. As the 
pressure increases, the valve diverts the discharge gas to 
the condensing unit, which will allow liquid flow from the 
condensing unit to the receiver.
When using this method of head pressure regulation there 
must be enough refrigerant in the system to ensure 
adequate charge at the lowest expected ambient 
temperature that the system will be operating.

A receiver is used to store the refrigerant during the time 
the condensing unit is not using the extra refrigerant 
charge. The head pressure control valve does not begin to 
allow refrigerant to pass to the receiver until the discharge 
pressure is at least 225 psig for R407C. This valve requires 
no adjustment.
RCU units utilize either R407C refrigerant. Refrigerant 
charging pressures vary depending on the type of 
refrigerant used in the unit. Tables are provided in 

“Refrigerant Characteristics,” p. 19

 showing the 

temperature/pressure characteristics for R407C 
refrigerant. Before charging, check the unit nameplate to 
confirm the type of refrigerant to use.

Hot Gas Bypass

A full floating hot gas bypass system may be provided as 
an option for capacity control and freeze protection. The 
hot gas bypass valve allows refrigerant to flow from the 
discharge line directly to the suction line. This provides 
freeze protection for the evaporator coil by limiting the 
minimum refrigerant pressure, preventing the surface 
temperature of the evaporator coil from dropping below 
32°F. 
The hot gas (discharge) regulating valve has a normal 
suction pressure control setting of:

R407C - 55 ±2 psig

This is read from the suction (low) side of the compressor 
as it operates in full hot gas bypass operation. The valve is 
factory set and no adjustment should be necessary. If 
adjustment is required, remove the adjustment cap from 
the valve. Using a 5/16 inch Allen wrench, turn clockwise 
to increase pressure or counterclockwise to lower 
pressure.

NOTICE

Compressor Damage!

Do not exceed 20°F superheat. Exceeding this 
temperature may cause failure of the compressor.

To prevent overheating the compressor, a small amount 
of liquid refrigerant passes through the quench valve and 
mixes with the hot gas entering the compressor, 
maintaining normal compressor suction pressure and 
temperature.
The normal control setting for the quench valve is 20°F 
superheat (when there is no call for cooling). The valve is 
factory set and no adjustment should be necessary. If 
adjustment is required, remove the adjustment cap from 
the valve. Turn the adjusting stem clockwise to increase 
the superheat and counterclockwise to decrease the 
superheat.

Содержание TR-OHS RCU Series

Страница 1: ...the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjus...

Страница 2: ...quipment that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Kno...

Страница 3: ...ede these policies Non Trane personnel should always follow local regulations Introduction SS SVX004C EN 3 Copyright This document and the information in it are the property of Trane and may not be us...

Страница 4: ...Procedures 16 Refrigerant Characteristics 19 Settings and Adjustments 20 High Low Pressure Limit Switches 20 Head Pressure Controls 20 Hot Gas Bypass 20 Commissioning and Decommissioning 21 Operation...

Страница 5: ...10 11 Unit RCU Remote Condensing Unit Digit 12 Outdoor Indoor O Outdoor Unit I Indoor Unit About Digits Model numbers are comprised of digits Each digit or set of digits defines the product model Exam...

Страница 6: ...electric box on the RCU O is weatherproof There are several cabinet sizes based on the capacity of the unit Refer to the installation drawing supplied with the unit for the layout and dimensions of th...

Страница 7: ...r located in the electric box The 012 040 model RCU I use a direct drive blower The 042 120 RCU I units have a belt driven blower with separate drive motor Electric Box RCU electrical components are p...

Страница 8: ...provided as standard on RCU O units and as an option on RCU I units A service disconnect switch electrically isolates the unit during routine maintenance The handle of the switch may be locked in the...

Страница 9: ...ly lift unit in a LEVEL position could result in unit dropping and possibly crushing operator technician which could result in death or serious injury and equipment or property only damage Test lift u...

Страница 10: ...ing for ducted systems Refer to the below figure Notes Do not install the A C system directly above electronic equipment that may hinder serviceability Equipment must be level to operate properly Figu...

Страница 11: ...ill be used if the volume of the piping is too large Note The size of the equipment pipe connections does not indicate the size of the refrigerant lines to be used In cases where the pipe size doesn t...

Страница 12: ...of 30 equivalent ft for longer rises individual calculations must be made Sizes assume the use of single risers double risers may be necessary Table 2 Recommended liquid line sizes Recommended Liquid...

Страница 13: ...se and frequency information specified on the system nameplate The supply voltage measured at the unit must be within 10 of the voltage specified on the nameplate refer to the below figure The namepla...

Страница 14: ...the compressor To correct this problem exchange any two of the incoming main power wires at the main power circuit breaker Do not rewire the unit s individual components Electric Box Layout The elect...

Страница 15: ...rform a dry nitrogen leak detection test on the system Using dry nitrogen only pressurize the system to 150 psig Ensure all service and solenoid valves are energized open and that no part of the syste...

Страница 16: ...Failure to follow instructions below could result in death or serious injury Do not work in confined spaces where refrigerant or other hazardous toxic or flammable gas may be leaking Refrigerant or ot...

Страница 17: ...e the cylinder is emptied Initial System Charge Introducing the Refrigerant Charge Follow the steps below to charge systems with R407C refrigerant The initial charge will be performed by introducing l...

Страница 18: ...f refrigerant charge This can be done by using the system controller to enable a call for dehumidification lower the humidity setpoint This process may need to be repeated several times After cycling...

Страница 19: ...Pressure psig R407C 70 55 85 Switch State Opens Closes Low Pressure Switch psig R407C 10 32 High Pressure Switch psig R407C 410 Manual Reset Saturated Refrigerant Pressure Table The refrigerant vapor...

Страница 20: ...liquid flow from the condensing unit to the receiver When using this method of head pressure regulation there must be enough refrigerant in the system to ensure adequate charge at the lowest expected...

Страница 21: ...pressure gas 3 The refrigerant then flows to the condensing unit coil The high temperature high pressure gas from the compressor is cooled and condensed by the flow of air through the condensing unit...

Страница 22: ...he following recommended guidelines When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders fo...

Страница 23: ...care to avoid accidents and ensure proper operation General Maintenance access to the remote condensing unit is through the removable panel on top of the unit Examine the areas around the air inlet an...

Страница 24: ...overload and re set circuit breaker s or motor starter protector s Condensing Unit Head Pressure Too High Non condensable gas or air in system Recover system evacuate per Preparing System for Charging...

Страница 25: ...o the unit Check fan motor starter protector contactor fan cycling switch or fan speed controller Suction Pressure too Low Expansion valve not opening fully indicated by abnormally cold suction line O...

Страница 26: ...ine whether it is an electrical or a mechanical failure An electrical failure will be indicated by the distinct pungent odor once the system has been opened If a burnout has occurred the oil will be b...

Страница 27: ...Cleanup Procedure WARNING Hazardous Voltage Disconnect all electric power including remote disconnects before servicing Follow proper lockout tagout procedures to ensure the power can not be inadverte...

Страница 28: ...r opening the sheave one half turn to decrease speed 7 Replace the sheave key and tighten set screw 8 Proper belt tension is achieved when the belt has a deflection of 1 2 inch per foot of span betwee...

Страница 29: ...Model Number Sales Order Number Item Number Unit Serial Number Description of Problem Obtaining Warranty Parts A support technician will provide troubleshooting assistance over the telephone If it can...

Страница 30: ...gerant charge bubbles in sight glass 2 Check suction and discharge pressure 3 Ensure refrigerant lines are secured 4 Tighten electrical connections 5 Ensure motor mount is secured 6 Clean unit as nece...

Страница 31: ...tolerances Main power wiring connections to the equipment including earth ground have been properly installed Customer supplied main power circuit breaker HACR type or fuses have proper ratings for e...

Страница 32: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Отзывы: