Figure 6.
Sample nameplate
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Installation
14
SS-SVX004C-EN
Note:
All wiring must conform to local and national
electrical code requirements. Use of copper
conductors only is required. Wiring terminations
may become loose during transit of the equipment;
therefore, it is required to verify that all wiring
terminations are secure.
It is important to note that the control transformer
supplied with the equipment is sized and selected based
upon the expected load for the system.
Important:
Do not connect any additional loads to the
system control transformer. Connecting
additional loads to the factory supplied
control transformer may result in
overloading of the transformer, which will
cause the transformer circuit breaker to trip.
Improper wire connections will result in the reverse
rotation of the fan and compressor and may eventually
result in damage to the compressor. To correct this
problem, exchange any two of the incoming main power
wires at the main power circuit breaker. Do not rewire the
unit’s individual components.
Electric Box Layout
The electronic components in the RCU electric boxes are
labeled with reference designators which are named in the
unit electrical drawings. See those drawings for the
location and identity of specific electric box components.
Sales Order Number:
Model Number: TR-
Item Number:
Serial Number:
Electrical Data:
SCCR: kA RMS Symmetrical
Voltage:
Phase:
Hz:
No. Wires: (Including Ground)
FLA:
MCA:
Max Fuse/Ckt. Bkr (HACR type per NEC):
A
Heater:
kW (Nominal)
Humidifier: kW (Nominal)
Evaporator Motor (1):HP:
FLA:
Evaporator Motor (2):HP:
FLA:
Condenser Motor (1): HP:
FLA:
Condenser Motor (2): HP:
FLA:
Condensate Pump:
HP:
FLA:
Compressor (1):
RLA:
LRA:
Compressor (2):
RLA:
LRA:
Refrigerant Type: R407C
Charge: Circuit #1: lb oz
Charge: Circuit #2: lb oz
High Side Design Pressure: 278 psig
Low Side Design Pressure:
144
psig
Max. Output Air Temperature: ºF
Blower/Fan Ext. Static Press.: in. w.g.
Max. Inlet Hot Water Temp.: ºF
Hot Water or Steam Pressure:
psig
Minimum Installation Clearance: 0.0 in.
Remote Condenser Type:
Suitable for Indoor:
Outdoor:
Use
Date of Manufacture:
Q.A. Acceptance:
SATS
1
Manufactured by
STULZ Air Technology Systems, Inc.
Frederick, Maryland, USA
Evaporator Motor (3):HP:
FLA:
Evaporator Motor (4):HP:
FLA: