Trane TR-OHS RCU Series Скачать руководство пользователя страница 15

Installation

SS-SVX004C-EN

15 

System Charging

DX Charging Requirements

When performing the specific DX charging procedures in 
this section, follow these best practices:

Ensure that contamination of different refrigerants 
does not occur when using charging equipment. 
Hoses or lines must be as short as possible to minimize 
the amount of refrigerant contained in them.

Keep cylinders upright.

Ensure the refrigeration system is grounded to Earth 
before charging the system with refrigerant.

Label the system when charging is complete (if it is not 
labeled already).

Exercise extreme care to avoid overfilling the 
refrigeration system.

Before recharging the system, it must be pressure tested 
with oxygen-free nitrogen (OFN). The system must be leak 
tested upon completion of charging but prior to 
commissioning. A follow-up leak test must be carried out 
prior to leaving the site.

R407C Refrigerant

R407C are blended refrigerants recognized for being safer 
for the environment. These refrigerants contain no 
chlorine, the component in HCFC’s that destroy the earth’s 
ozone layer. However, the same care should be taken to 
prevent leakage because R407C can contribute to the 
greenhouse effect if released. If the refrigerant gas is 
released in an enclosed space, it can become a suffocant.
Refrigerants that are multi-component blends have 
component parts with different volatilities that result in a 
change in composition and saturation temperature as 
evaporation and condensation occur. Typically, the 
composition of R407C vapor is different than that of R407C 
liquid within a contained system. The composition of 
liquid R407C refrigerant remains relatively constant, 
however, the refrigerant vapor tends to separate into its 
component parts even when circulating.

Preparing System for Charging

Note:

Refrigerant charging must be performed by a 
journeyman, refrigerant mechanic or an air 
conditioning technician.

1. With all the system piping connections made, perform 

a dry nitrogen leak detection test on the system. Using 
dry nitrogen only, pressurize the system to 150 psig. 
Ensure all service and solenoid valves are energized 
open and that no part of the system is isolated from the 
pressurized nitrogen (liquid, suction or discharge lines 
and reheat coil).

2. Since there is no refrigerant in the system to detect at 

this point, leaks may be detected by observing if 
there’s been a change in the standing pressure after 12 
hours. A significant drop in pressure indicates a leak in 
the system that needs to be repaired. After the system 
is determined to be free of leaks, evacuate the system.

NOTICE

Compressor Damage!

A proper vacuum must be drawn on the refrigerant 
system to remove moisture prior to charging. If this is 
not done the refrigerant charge will combine with 
moisture in the pipes to form an acid that will 
eventually lead to compressor failure. A triple 
evacuation procedure with dry nitrogen is 
recommended especially for systems with newly 
installed refrigerant piping.

Notes:

Use a vacuum pump capable of evacuating the entire 
volume of the A/C system, including newly installed or 
existing piping. It is essential to use a well-maintained 
pump that is in good operating condition.

Use high quality hoses ensuring they are free of 
defects and don’t leak. It is recommended to use 
copper tubing instead of hoses if possible due to the 
low vacuum that must be attained when evacuating 
the system. The use of short, large diameter hoses 
helps reduce evacuation time.

3. After ensuring there are no leaks, relieve pressure and 

evacuate the entire system while maintaining all the 
solenoids and hot gas reheat valves open. Pull an 
initial vacuum of 150 microns or lower using the 
suction service port, the discharge service port after 
the check valve and the service port of the receiver (if 
applicable).

Note:

When pulling a vacuum, the Schrader valves will 
unnecessarily restrict the openings, increasing the 
evacuation time. During the evacuation process it 
is recommended to remove the Schrader valve 
cores with a Schrader valve core removal tool and 
draw the vacuum through the port on the removal 
tool.

Содержание TR-OHS RCU Series

Страница 1: ...the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjus...

Страница 2: ...quipment that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Kno...

Страница 3: ...ede these policies Non Trane personnel should always follow local regulations Introduction SS SVX004C EN 3 Copyright This document and the information in it are the property of Trane and may not be us...

Страница 4: ...Procedures 16 Refrigerant Characteristics 19 Settings and Adjustments 20 High Low Pressure Limit Switches 20 Head Pressure Controls 20 Hot Gas Bypass 20 Commissioning and Decommissioning 21 Operation...

Страница 5: ...10 11 Unit RCU Remote Condensing Unit Digit 12 Outdoor Indoor O Outdoor Unit I Indoor Unit About Digits Model numbers are comprised of digits Each digit or set of digits defines the product model Exam...

Страница 6: ...electric box on the RCU O is weatherproof There are several cabinet sizes based on the capacity of the unit Refer to the installation drawing supplied with the unit for the layout and dimensions of th...

Страница 7: ...r located in the electric box The 012 040 model RCU I use a direct drive blower The 042 120 RCU I units have a belt driven blower with separate drive motor Electric Box RCU electrical components are p...

Страница 8: ...provided as standard on RCU O units and as an option on RCU I units A service disconnect switch electrically isolates the unit during routine maintenance The handle of the switch may be locked in the...

Страница 9: ...ly lift unit in a LEVEL position could result in unit dropping and possibly crushing operator technician which could result in death or serious injury and equipment or property only damage Test lift u...

Страница 10: ...ing for ducted systems Refer to the below figure Notes Do not install the A C system directly above electronic equipment that may hinder serviceability Equipment must be level to operate properly Figu...

Страница 11: ...ill be used if the volume of the piping is too large Note The size of the equipment pipe connections does not indicate the size of the refrigerant lines to be used In cases where the pipe size doesn t...

Страница 12: ...of 30 equivalent ft for longer rises individual calculations must be made Sizes assume the use of single risers double risers may be necessary Table 2 Recommended liquid line sizes Recommended Liquid...

Страница 13: ...se and frequency information specified on the system nameplate The supply voltage measured at the unit must be within 10 of the voltage specified on the nameplate refer to the below figure The namepla...

Страница 14: ...the compressor To correct this problem exchange any two of the incoming main power wires at the main power circuit breaker Do not rewire the unit s individual components Electric Box Layout The elect...

Страница 15: ...rform a dry nitrogen leak detection test on the system Using dry nitrogen only pressurize the system to 150 psig Ensure all service and solenoid valves are energized open and that no part of the syste...

Страница 16: ...Failure to follow instructions below could result in death or serious injury Do not work in confined spaces where refrigerant or other hazardous toxic or flammable gas may be leaking Refrigerant or ot...

Страница 17: ...e the cylinder is emptied Initial System Charge Introducing the Refrigerant Charge Follow the steps below to charge systems with R407C refrigerant The initial charge will be performed by introducing l...

Страница 18: ...f refrigerant charge This can be done by using the system controller to enable a call for dehumidification lower the humidity setpoint This process may need to be repeated several times After cycling...

Страница 19: ...Pressure psig R407C 70 55 85 Switch State Opens Closes Low Pressure Switch psig R407C 10 32 High Pressure Switch psig R407C 410 Manual Reset Saturated Refrigerant Pressure Table The refrigerant vapor...

Страница 20: ...liquid flow from the condensing unit to the receiver When using this method of head pressure regulation there must be enough refrigerant in the system to ensure adequate charge at the lowest expected...

Страница 21: ...pressure gas 3 The refrigerant then flows to the condensing unit coil The high temperature high pressure gas from the compressor is cooled and condensed by the flow of air through the condensing unit...

Страница 22: ...he following recommended guidelines When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders fo...

Страница 23: ...care to avoid accidents and ensure proper operation General Maintenance access to the remote condensing unit is through the removable panel on top of the unit Examine the areas around the air inlet an...

Страница 24: ...overload and re set circuit breaker s or motor starter protector s Condensing Unit Head Pressure Too High Non condensable gas or air in system Recover system evacuate per Preparing System for Charging...

Страница 25: ...o the unit Check fan motor starter protector contactor fan cycling switch or fan speed controller Suction Pressure too Low Expansion valve not opening fully indicated by abnormally cold suction line O...

Страница 26: ...ine whether it is an electrical or a mechanical failure An electrical failure will be indicated by the distinct pungent odor once the system has been opened If a burnout has occurred the oil will be b...

Страница 27: ...Cleanup Procedure WARNING Hazardous Voltage Disconnect all electric power including remote disconnects before servicing Follow proper lockout tagout procedures to ensure the power can not be inadverte...

Страница 28: ...r opening the sheave one half turn to decrease speed 7 Replace the sheave key and tighten set screw 8 Proper belt tension is achieved when the belt has a deflection of 1 2 inch per foot of span betwee...

Страница 29: ...Model Number Sales Order Number Item Number Unit Serial Number Description of Problem Obtaining Warranty Parts A support technician will provide troubleshooting assistance over the telephone If it can...

Страница 30: ...gerant charge bubbles in sight glass 2 Check suction and discharge pressure 3 Ensure refrigerant lines are secured 4 Tighten electrical connections 5 Ensure motor mount is secured 6 Clean unit as nece...

Страница 31: ...tolerances Main power wiring connections to the equipment including earth ground have been properly installed Customer supplied main power circuit breaker HACR type or fuses have proper ratings for e...

Страница 32: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Отзывы: