SETUP Menu
VENTILATION OVERRIDE MENU SCREENS
Ventilation Override Definitions
Press ENTER to Review or Adjust
Used With: Units w/VOM Installed
• Press the Next key to skip this Submenu.
Ventilation Override Definition Mode A
Supply Fan ON
Used With: Units w/VOM Installed
Possible Values: ON, OFF
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A
Supply Fan IGV/VFD MIN
Used With: Units w/VOM Installed
Possible Values: IN CONTROL, MIN, MAX
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A
Exhaust Fan/Dampers ON/OPEN
Used With: Units w/VOM and Power
Exhaust w/Statitrac
Possible Values: ON/OPEN, OFF/CLOSED
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A
Return Fan/Exhaust Dampers OFF/CLOSED
Used With: Units w/VOM and Return Fan
Possible Values: OFF/CLOSED, ON/OPEN
• Press the Next key to navigate forward.
Ventilation Override Definition Mode A
Exhaust Fan ON
Used With: Units w/VOM and Power
Exhaust w/o Statitrac Installed
Possible Values: ON, OFF
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A
Return Fan VFD Command Min
Used With: Units w/VOM and Return Fan
with Statitrac Installed
Possible Values: Return Fan VFD
Command: MIN, MAX
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A
Outside Air Dampers OPEN
Used With: Units w/VOM and Economizer
Option
Possible Values: OPEN, CLOSED
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A
VAV Box Relay DEENERGIZED
Used With: Units w/VOM Installed
Possible Values: ENERGIZED,
DEENERGIZED
• Press Next/Previous keys to navigate.