RT-SVP07B-EN
37
STATUS Menu
Outside Air Damper Target: 27 %
Outside Air Damper Position: 24 %
Used With: Units w/Fresh Air Options
Possible Values: 0 to 100%
• Press Next/Previous keys to navigate.
VCM Preheater Output Control: OFF
VCM Module Aux Temp Input: 47.2 °F
Used With: Fresh Air Measurement
(VCM) w/DCV or OA Damper Min Position
(VCM) w/DCV and Preheat ENABLED
Possible Values:
Output Control: ON, OFF
Aux Temp Input: -40.0 to 200.0ºF
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
RETURN FAN STATUS SUBMENU SCREENS
Return Fan Status Submenu
Press ENTER to View Data in This Submenu
Used With: Units w/Return Fan Option
• Press the Next key to skip this Submenu.
Return Fan Relay: ON
Return Airflow Proving: ON
Used With: Units w/Return Fan Option
Possible Values: ON, OFF
• Press Next/Previous keys to navigate.
Return Fan VFD Command: 45 %
Return Plenum Pressure: 0.8 IWC
Used With: Units w/Return Fan Option
Possible Values:
Command: 0 to 100%
Pressure: -0.7 to 3.5 IWC
Top line shown only if Return Fan VFD is installed.
• Press Next/Previous keys to navigate.
Return Plenum Pressure Target: 0.8 IWC
Return Fan VFD Pos: Opening to 45 %
Used With: Units w/Return Fan Option
Possible Values:
Target: -0.5 IWC, or 0.1 to 2.5 IWC
VFD Pos: 0 to 100%
“Opening to” and ”Closing to” indicates direction.
“Limited to” indicates an active override.
• Press Next/Previous keys to navigate.