SERVICE MODE Menu (Local Human Interface only)
Supply Fan OFF IGV/VFD Cmd 0%
Return Fan OFF VFD Cmd 0%
Used With: Units w/Return Fan Option
Possible Values:
Fan: OFF, ON, AUTO
IGV/VFD: 0 to 100%
VFD: 0 to 100%
Note: Fans must be ON, and IGV/VFD
command must be 100% if staged heat is
being tested.
Note:
The “Return Fan” field is not manually setable but will
automatically change as the “Supply Fan” field is changed. This is
to insure proper airflow through the unit.
“IGV/VFD’ shown for VVDA or VVZT units.
“VFD” shown for units with Statirac.
• Press Next/Previous keys to navigate.
RTM VAV Box Relay DRIVE MAX
RTM Alarm Output ON
Used With: All Units
Possible Values:
RTM VAV Box Relay: Drive Max, Auto
Alarm Output: On, Off
• Press Next/Previous keys to navigate.
Humidification Relay ON
Used With: All Units
Possible Values: ON, OFF
Note: The “Humidification Relay” can only be set to ON if the
supply fan output is set ON. A message will display indicating such
and operation will be prevented.
• Press Next/Previous keys to navigate.
ENERGY RECOVERY CONTROL SUBMENU SCREENS
Energy Recovery Control Submenu
Press ENTER to Review or Adjust
Used With: Units w/Energy Recovery
Option
• Press the Next key to skip this Submenu.
Energy Recovery Wheel Operation: OFF
Energy Recovery Preheat Relay: OFF
Used With: Units w/Energy Recovery
Option
Possible Values:
Wheel Operation: ON, OFF
Preheat Relay: ON, OFF
Note: The “ER Preheat Relay” can only be set to ON if the supply
fan output is set to ON. A message will display indicating such and
operation will be prevented.
• Press Next/Previous keys to navigate.
Exhaust Air Bypass Damper Pos: 0%
Outside Air Bypass Damper Pos: 0%
Used With: Units w/Energy Recovery
Option
Possible Values: 0 to 100%
• Press Next/Previous keys to navigate.