64
RT-SVP07B-EN
SETUP Menu
DCV Active Supply Fan Control: ENABLED
Allow Supply Fan to Energize for DCV
Used With: CVZT or VVZT Units w/DCV
set to ENABLED.
Factory Preset: DISABLED
Possible Values: DISABLED, ENABLED,
Bottom Field:
If ENABLED: “Allow Supply Fan to
Energize for DCV”
If DISABLED: (blank)
• Press Next/Previous keys to navigate.
OA Flow Compensation Function: DISABLED
Use fixed OA Damper Minimum Position
Used With: VVDA or VVZT Units w/
Economizer
Factory Preset: DISABLED
Possible Values: ENABLED, DISABLED
Bottom Field:
If ENABLED: “OA Damper Min Pos
Depends on IGV/VFD Pos”
If DISABLED: “Use Fixed OA Damper
Minimum Position”
• Press Next/Previous keys to navigate.
OA Flow CO
2
Reset Function: ENABLED
CO
2
Start: 800 PPM CO
2
Max: 1000 PPM
Used With: IPak-I Units w/Fresh Air
Measurement (VCM) w/o DCV Option
Factory Preset:
Function: DISABLED
Start: 800, Max: 1000
Possible Values:
Function: ENABLED, DISABLED
Start: 50 to 1900
Max: 150 to 2000
Note:
Bottom line will not be shown if function is DISABLED.
• Press Next/Previous keys to navigate.
OA Flow Calibration Data (Left)
Gain 1.0 Offset 0 CCFM
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV Option
Factory Preset: Gain 1.0, Offset 0 CCFM
Possible Values:
Gain: 0.5 to 1.5
Offset: -25 to 25 CCFM
“Left” refers to the flow station on the left side of the unit when
looking into the unit’s airstream.
• Press Next/Previous keys to navigate.
OA Flow Calibration Data (Right)
Gain 1.0 Offset 0 CCFM
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV Option
Factory Preset: Gain 1.0, Offset 0 CCFM
Possible Values:
Gain: 0.5 to 1.5
Offset: -25 to 25 CCFM
“Right” refers to the flow station on the right side of the unit when
looking into the unit’s airstream.
• Press Next/Previous keys to navigate.