STATUS Menu
Active SA Min Target Setpoint:
50.0 °F
Active SA Target Low Limit:
38.4 °F
Used With: Units w/SZVAV(VVZT)
Option
Possible Values:
MinTarget: Equal to SA Heating
Setpoint
Low Limit: (calculated)
Fan speed modulation in cooling occurs
when the Target Setpoint modulates
between the Min Setpoint and Low Limit
Setpoint.
The Target Low Limit is a calculated value which corresponds to the
Maximum Fan Speed during cooling (see SA Target Setpoint on
previous screen). The Min Target Setpoint reflects the SA Cooling
Setpoint value and corresponds to the Minimum Fan Speed during
cooling.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
ENERGY RECOVERY STATUS SUBMENU SCREENS
Energy Recovery Status Submenu
Press ENTER to View Data in This Submenu
Used With: Units w/Energy Recovery
Option
• Press the Next key to skip this Submenu.
Energy Wheel Relay: ON
Energy Wheel Proving: ON
Used With: Units w/Energy Recovery
Option
Possible Values: ON, OFF
• Press Next/Previous keys to navigate.
Outside Air Bypass Damper Pos: 0%
Exhaust Air Bypass Damper Pos: 15%
Used With: Units w/Energy Recovery
Option
Possible Values: 0 to 100%
• Press Next/Previous keys to navigate.
Energy Wheel Frost Avoidance: INACTIVE
Leaving Recovery Exhaust Temp: 45.0°F
Used With: Units w/Energy Recovery
Option
Possible Values:
Frost Avoidance: ACTIVE, INACTIVE;
Exhaust Temp: -40.0 to 200.0ºF
• Press Next/Previous keys to navigate.
MPM Preheat Relay: OFF
Used With: Units w/Energy Recovery
Option w/Preheat
Possible Values: ON, OFF
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.