STATUS Menu
Max Return Plenum Pressure Stp: 1.2 IWC
High Limit: 3.5 IWC Deadband: 0.2 IWC
Used With: Units w/Return Fan Option
Possible Values:
Pressure Stp: 0.1 to 2.5 IWC
Deadband: 0.1 to 1.0 IWC
High Limit: 3.5 IWC (non-adjustable)
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
SINGLE ZONE VAV STATUS SUBMENU SCREENS
Single Zone VAV Control Status Submenu
Press ENTER to View Data in this Section
Used With: Units w/SZVAV(VVZT)
Option
• Press Next/Previous keys to navigate.
Active SA Target High Limit: 123.0 °F
Active SA Max Target Setpoint: 100.0 °F
Used With: Units w/SZVAV(VVZT)
Option
Possible Values:
High Limit: (calculated)
Max Target: Equal to SA Cooling
Setpoint
Fan speed modulation in heating occurs
when the Target Setpoint modulates
between the Max Setpoint and High Limit
Setpoint.
The Target High Limit is a calculated value which corresponds to
the Maximum Fan Speed during heating (see SA Target Setpoint
on following screen). The Max Target Setpoint reflects the SA
Heating Setpoint value and corresponds to the Minimum Fan
Speed during heating.
• Press Next/Previous keys to navigate.
Active SA Target Setpoint: 74.0 °F
Active SA Temperature: 73.9 °F
Used With: Units w/SZVAV(VVZT)
Option
Possible Values:
SA Target: Max Target – Min Target
SA Temp: See SA Temp status.
The SA Target Setpoint is a calculated discharge setpoint based on
zone temperature conditions. Heating and Cooling is staged to
maintain SA Temperature to this setpoint. The range is clamped
on the high end to Max Target Setpoint (see previous screen) and
to the low end to Min Target Setpoint (see next screen).
• Press Next/Previous keys to navigate.