![Trane S*HF*20-75 Скачать руководство пользователя страница 116](http://html1.mh-extra.com/html/trane/s-hf-20-75/s-hf-20-75_troubleshooting-manual_1149487116.webp)
116
RT-SVP07B-EN
DIAGNOSTICS Menu
Active Diagnostic -- Info
Dirty Recovery Filter More
Used With: All units
Factory Presets: N/A
Possible Values: [Information Only]
Heat Fail
Dirty Filter
Dirty Final Filter
Dirty Recovery Filter
Ventilation Override Mode A, B, C, D, E
Note: The word “More” will only appear if more than one failure
is occurring. Press the Next key to view the remaining diagnostics
if any exist.
Note: Pressing the Next key at the last Info Only Diagnostic will
prompt the following screen…
Log 1 (Viewed) History Manual
Supply Air Pres Setpt Failure
Used With: All units
Factory Presets: N/A
Possible Values: Log Number 1-20
Top Middle-Left Field:
Viewed, Not Viewed
Top Middle-Right Field:
Active, History
Top Right Field:
Manual, Auto, Info.
Notes:
1. Any diagnostic listed under the previous screens will be
displayed here. This screen will show the last 20 diagnostics
that have occurred with the latest being assigned to “Log 1”, the
prior being pushed to “Log 2” (and so on) with the last
diagnostic in the list being removed if beyond the 20th position.
No diagnostic will be logged consecutively, another diagnostic
must occur prior to an older diagnostic being re-entered into
the log.
2. Press the Next key to view any remaining diagnostic history
items. Pressing the Cancel key, to clear the diagnostic history
log, will prompt the following screen…
Diagnostic Log Is Password Protected
Please Enter Password:
Used With: All units
Factory Presets: N/A
Possible Values: + (Plus) and - (Minus)
Notes:
1. Press the + (plus) or - (minus) keys to enter the password.
2. Press the ENTER key to confirm this choice. When the correct
password is entered, the following screen will be displayed…
Active Diagnostics Manual
Please Wait, Updating Diagnostic Log
Used With: All units
Factory Presets: N/A
Possible Values: Manual, Auto, or Info
OR
Note: If the Cancel key is pressed there are no diagnostics listed
in the “DIAGNOSTIC LOG”, the following screen will be displayed…