36
RT-SVP07B-EN
STATUS Menu
OUTSIDE AIR VENTILATION STATUS SUBMENU SCREENS
Outside Air Ventilation Status Submenu
Press ENTER to View Data in this Submenu
Used With: Units w/Fresh Air Options
• Press the Next key to skip this Submenu.
Demand Control Ventilation is ENABLED
Space CO
2
Level: 600 PPM
Used With: All Units
Possible Values:
DCV: ENABLED, DISABLED
CO
2
Level: 50 to 2200 PPM
"Space CO2 Level” is shown only if “Demand Control Ventilation”
is ENABLED
• Press Next/Previous keys to navigate.
Note:
One of the three following screens will be shown based on
fresh air measurement and DCV options.
DCV Min OA Flow Target: 250.0 CCFM
Deadband: 5.0 CCFM OA Flow 234.3 CCFM
Used With: Fresh Air Measurement
(VCM) w/DCV and Demand Control
Ventilation ENABLED
Possible Values:
Target: 0 to 650 CCFM
Deadband: 5.0 to 200 CCFM
OA Flow: 0 to 650 CCFM
OR
Active Min OA Flow Setpoint: 140.3 CCFM
Deadband: 6.8 CCFM OA Flow 143.5 CCFM
Used With: Fresh Air Measurement
(VCM) w/DCV and Demand Control
Ventilation DISABLED
Possible Values:
Setpoint: 0 to 650 CCFM
Deadband: 5.0 to 200 CCFM
OA Flow: 0 to 650 CCFM
OR
Active Min OA Flow Setpoint: 140.3 CCFM
CO2 Level 1100 PPM OA Damper Pos: 99 %
Used With: Fresh Air Measurement
(VCM) w/o DCV and CO2 Reset ENABLED
Possible Values:
Setpoint: 0 to 650 CCFM
CO2 Level: 50 to 2000 PPM
OA Damper Pos: 0 to 650 CCFM
• Press Next/Previous keys to navigate.
Outside Air Flow Total: 335.4 CCFM
Left: 167.2 CCFM Right: 168.2 CCFM
Used With: Fresh Air Measurement
(VCM) w/DCV
Possible Values: 0 to 650 CCFM
• Press Next/Previous keys to navigate.