46
RT-SVP07B-EN
STATUS Menu
Active Rapid Restart Sensor Input From
ECEM RETURN AIR TEMP INPUT is 82.0°F
Used With: Units w/Rapid Restart.
Possible Values:
[See “Possible Values:” Above]
• Press Next/Previous keys to navigate.
Active Space CO
2
Sensor Input From
VCM SPACE CO
2
INPUT is 600 PPM
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV, or CO
2
Reset ENABLED
Possible Values:
VCM SPACE CO
2
INPUT
BAS/NETWORK
Range: 50 to 2000 PPM
• Press Next/Previous keys to navigate.
Active Dehumid OVRD Temp Input From
RTM ZONE TEMP INPUT is 73.5°F
Used With: Units w/Dehumid. Option
Possible Values:
RTM ZONE TEMP INPUT
NSB PANEL TEMP SENSOR INPUT
RTM AUX TEMP INPUT
HEAT MODULE AUX TEMP INPUT
ECEM RETURN AIR TEMP INPUT
BAS/NETWORK SENSOR
Range: -40 to 200ºF
• Press Next/Previous keys to navigate.
Active Zone Reset Temp Sensor Input From
RTM ZONE TEMP INPUT is 82.0°F
Used With: All Units with Reset Select
not selected as None.
Possible Values:
[See “Possible Values:” Above]
• Press Next/Previous keys to navigate.
Active OA Temperature Sensor Input From
RTM OUTSIDE AIR TEMP INPUT is 86.0°F
Used With: All Units
Possible Values:
RTM OUTSIDE AIR TEMP INPUT BAS/
NETWORK
Range: -40 to 200ºF
• Press Next/Previous keys to navigate.
Active Outside Air Humidity Input From
OA HUMIDITY SENSOR INPUT is 30 %
Used With: Units w/Economizer Option
Possible Values:
OA HUMIDITY SENSOR INPUT
BAS/NETWORK SENSOR
Range: 10 to 90%
• Press Next/Previous keys to navigate.