Installation Mechanical
RTHD-SVX02H-EN 59
Refrigerant Pressure Relief Valve Venting
D
WARNING
Hazardous Gases!
Consult local regulations for any special relief line
requirements. Refrigerant vented into a confined equip
-
ment room could displace available oxygen to breathe,
causing possible asphyxiation or other serious health
risks. Failure to follow these recommendations could
result in death or serious injury.
Note:
Vent pipe size must conform to the ANSI/ASHRAE
Standard 15 for vent pipe sizing. All federal, state,
and local codes take precedence over any sug-
gestions stated in this manual.
All relief valve venting is the responsibility of the install-
ing contractor.
All RTHD units use evaporator, compressor, and con-
denser pressure relief valves (
Figure 28
) that must be
vented to the outside of the building.
Relief valve connection sizes and locations are shown in
the unit submittals. Refer to local codes for relief valve
vent line sizing information.
D
CAUTION
Equipment Damage!
Do not exceed vent piping code specifications. Failure
to comply with specifications may result in capacity
reduction, unit damage and/or relief valve damage.
Relief valve discharge setpoints and capacities rates are
given in
Table 14
. Once the relief valve has opened, it will
reclose when pressure is reduced to a safe level.
Note:
Once opened, relief valves may have tendency to
leak and must be replaced.
Figure 28. Relief Valve Location
Evaporator Shell
* Valve is hidden by pipe
*
*
Condenser Shell
Discharge Pipes
Pressure relief valve discharge capacities will vary with
shell diameter and length and also compressor displace-
ment. Discharge venting capacity should be calculated
as required by ASHRAE Standard 15-94. Do not adjust
relief valve setting in the field.
Содержание RTHD series
Страница 28: ...Installation Mechanical 28 RTHD SVX02H EN Figure 9 Unit Weights and Dimensions for Rigging Y Z A B C D X C G...
Страница 69: ...Installation Electrical RTHD SVX02H EN 69 Figure 35 Solid State Starter Panel Power Wire Routing...
Страница 120: ...120 RTHD SVX02H EN...
Страница 121: ...RTHD SVX02H EN 121 23094870 1 1 FIELD WIRING RTHD PBL 3 12 03 H 23094870 1 1 FIELD WIRING RTHD PBL 3 12 03 H...
Страница 122: ...122 RTHD SVX02H EN...
Страница 123: ...RTHD SVX02H EN 123 EXV...
Страница 124: ...124 RTHD SVX02H EN...
Страница 125: ...RTHD SVX02H EN 125...
Страница 126: ...126 RTHD SVX02H EN RLA 0 10VDC RLA 0 10V 2 10VDC 4 20mA 2 10VDC 4 20mA TRACER SUMMIT LONTALK...
Страница 127: ...RTHD SVX02H EN 127 2 10VDC 4 20mA TRACER SUMMIT LONTALK 4 20mA 2 10VDC 4 20mA 2 10VDC...
Страница 128: ...128 RTHD SVX02H EN 1A24...
Страница 129: ...RTHD SVX02H EN 129...
Страница 130: ...130 RTHD SVX02H EN UC800 RLA 115V 27V 115V TD 7...
Страница 131: ...RTHD SVX02H EN 131 CLASS1 CLASS1 CLASSII 300V W1 W2 120VAC 7 2AMPS 2 88AMP 1 3HP 7 2FLA 240VAC 5AMPS IOM...
Страница 132: ...132 RTHD SVX02H EN...
Страница 133: ...RTHD SVX02H EN 133 EXV 2 EXV 1...
Страница 134: ...134 RTHD SVX02H EN...
Страница 135: ...RTHD SVX02H EN 135...
Страница 136: ...136 RTHD SVX02H EN...
Страница 137: ...RTHD SVX02H EN 137...
Страница 138: ...138 RTHD SVX02H EN 1A24...
Страница 139: ...RTHD SVX02H EN 139...
Страница 140: ...140 RTHD SVX02H EN UC800 RLA 115V 27V 115V TD 7 27V...
Страница 141: ...RTHD SVX02H EN 141 115V CLASS1 CLASS1 CLASSII 300V W1 W2 120VAC 7 2AMPS 2 88AMP 1 3HP 7 2FLA 240VAC 5AMPS IOM...
Страница 142: ...142 RTHD SVX02H EN...
Страница 144: ...144 RTHD SVX02H EN HEAT RECOVERY OIL TANK EVAPORATOR CONDENSER Heat Recovery Model...
Страница 145: ...RTHD SVX02H EN 145 ERY CONTROL PNAEL SEE DETAIL A G...
Страница 146: ...146 RTHD SVX02H EN...
Страница 147: ...RTHD SVX02H EN 147 C A DIVISION OF AMERICAN STANDARD INC ALL RIGHTS RESERVED...
Страница 148: ...148 RTHD SVX02H EN HEAT RECOVERY OIL TANK EVAPORATOR CONDENSER DETAIL A Heat Recovery Model...
Страница 149: ...RTHD SVX02H EN 149 ERY CONTROL PNAEL SEE DETAIL A...