Mechanical
Specifications

Supply and/or Return Air Smoke
Detector

 

— With this option factory-

installed, if smoke is detected, all unit
operation will be shut down. Reset will
be manual at the unit. Return Air Smoke
Detectors require minimum allowable
airflow when used with certain models.
See the Installation, Operation, and
Maintenance (IOM) manual for the
models affected and the minimum
allowable airflow required. This option is
available for microprocessor controlled
units.

Black Epoxy Coated Condenser Coil

 —

The coil provides corrosion protection to
condenser coils for seacoast application.
The protection is a factory-applied
thermoset vinyl coating, bonded to
normal aluminum fin stock. The uniform
thickness of the bonded vinyl layer
exhibits excellent corrosion protection in
salt spray tests performed in accordance
with ASTM B117.

Dehumidification Option

 — The

dehumidification (hot gas reheat) option
shall be a factory-installed option that
provides increased dehumidification. The
option shall consist of a hot-gas reheat
coil located on the leaving air side of the
evaporator coil prepiped and circuited.

The option shall be equipped with
crankcase heater(s), low pressure
switch(es), Frostat™, and a thermostatic
expansion valve(s) (TXV) as standard.

Control Options

Trane Communication Interface 

— This

factory or field-installed option shall be
provided to interface microprocessor
controlled units with the Trane Integrated
Comfort

TM

 systems.

LonTalk® Communication Interface 

This factory or field-installed option shall

be provided to allow the unit to
communicate as a Tracer™LCI-R device
or directly with generic LonTalk Network
Building Automation System Controls.

Zone Sensor

 — This field-installed

control shall be provided to interface
with the Micro equipped units and shall
be available in either manual, automatic
programmable with night setback, with
system malfunction lights, or remote
sensor options.

Thermostat

 — Two stage heating and

cooling operation or one stage heating
and cooling shall be available, for field
installation, in either manual or
automatic changeover. Automatic
programmable electronic with night set
back shall also be available.

Differential Pressure Switches

 — These

factory or field-installed sensors allow
individual fan failure and dirty filter
indication for microprocessor controlled
units. The fan failure switch will disable
all unit functions and “flash” the Service
LED on the zone sensor. The dirty filter
switch will light the Service LED on the
zone sensor and will allow continued
unit operation.

Enthalpy Control

 — Replaces the dry

bulb control with a wet bulb changeover
controller which has a fully adjustable
set point. Enthalpy control offers a
higher level of comfort control, along
with energy savings potential, than the
standard dry bulb control.  This is due to
the additional wet bulb sensing
capability. This option shall be available
for microprocessor controlled units. It
can be field-installed, or factory-installed
with the factory-installed economizer.

Differential Enthalpy

 — Replaces the

standard dry bulb control with two
enthalpy sensors that compare total heat
content of the indoor air and outdoor air
to determine the most efficient air
source. This control option offers the
highest level of comfort control, plus
energy efficiency, available. This option
shall be available for microprocessor
controlled units. It can be field-installed,
or factory-installed with the factory-
installed economizer.

Low Ambient Cooling

 — All

microprocessor units shall have cooling
capabilities down to 0°F as standard.
Electromechanical models have cooling
capabilites to 40°F as built, or to 0°F by
adding the optional low ambient (frostat)
control.

Thermal Expansion Valve

 — All units

shall have a short orifice refrigerate
control metering device.  For more exact
refrigerant flow, when using unit in low
airflow applications, a Thermal
Expansion Valve option shall be
available.

Novar Unit Controls

 

— Optional Novar

rooftop unit controls shall be factory
installed and tested.  The Novar
electronic thermostat module will
interface to the unit microprocesser and
will control the unit to the desired stage
of cooling or heating.

Novar Return Air Sensor

 

— This  option,

when used in conjunction with Novar
Controls, will contain a factory provided
and wired zone temperature snesor
located in the return air stream.

CO2 Sensing

 — The CO2 sensor shall

have the ability to to monitor space
occupancy levels within the building by
measuring the parts per million of CO2
(Carbon Dioxide) in the air. As the CO2
levels increase, the outside air damper
modulates to meet the CO2 space
ventilation requirements. The CO2
accessory shall be available as field
installed.

Ventilation Override Accessory

 

—With

the Ventilation Override Accessory
installed, the unit can be set to transition
to up to 3 different pre-programmed
sequences for Smoke Purge,
Pressurization, and Exhaust. The
transition occurs when a binary input on
the RTOM is closed (shorted). This would
typically be a hard wired relay output
from a smoke detector of fire control
panel. The ventilation override accessory
shall be available as field installed.

Humidity Sensor (BAYSENS036)

 

—Field

installed, wall-mounted humidity sensor
is used to control activation of the hot
gas reheat dehumidification option. The
humidity sensor can be set for humidity
levels between 40% and 60% relative
humidity by adjusting the ReliaTel
Options Module.

Humidity Sensor (BAYSENS037)

  

—Field

installed, duct-mounted humidity sensor
is used to control activation of the hot
gas reheat dehumidification option. The
humidity sensor can be set for humidity
levels between 40% and 60% relative
humidity by adjusting the ReliaTel
Options Module.

Содержание Precedent RT-PRC005

Страница 1: ...Packaged Cooling with ElectricHeatRooftopUnits Precedent 3 10T ons 60 Hz RT PRC005 EN March 2003...

Страница 2: ...r applications and for the more sophisticated ReliaTel microprocessor controls In addition to controls Precedent offers many other outstanding features and option choices With its sleek compact cabine...

Страница 3: ...Considerations Selection Procedure Model Number Description General Data Performance Data Cooling Performance Fan Performance Heat Performance Controls Electric Power Dimension andWeights Mechanical...

Страница 4: ...hat s easy to clean and reversible to allow installation of drain trap on either side of the unit Through the Base Condensate Every unit includes provisions for through the base condensate drain conne...

Страница 5: ...temperature Improves quality and reliability through the use of time tested microprocessor controls and logic Prevents the unit from short cycling considerably improving compressor life Ensures that t...

Страница 6: ...Comfort System to indicate a dirty filter or a fan that s not working The field installation charges for these valuable feedback devices often eliminate them from consideration Factory installation c...

Страница 7: ...ves a 100 unit run test before leaving the production line to make sure it lives up to rigorousTrane requirements We test designs at our factory not on our customers QualityAnd ReliabilityTesting All...

Страница 8: ...ection also increases opening the dampers and relieving the conditioned space NOTE THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED PRESSURE DROP OFTHE RETU...

Страница 9: ...r Size 6 kW 0 05 wg fromTable PD 51 Total Static Pressure 0 67 wg Note The Evaporator Fan Performance Table PD 20 has deducted the pressure drop for a 1 in filter already in the unit see note belowTab...

Страница 10: ...or 0 No Smoke Detector A ReturnAir Smoke Detector B Supply Air Smoke Detector C Supply and Return Air Smoke Detectors DIGIT 25 Monitoring Controls 0 No Monitoring Control 1 Clogged Filter Switch 2 Fan...

Страница 11: ...1 1 1 1 Diameter xWidth in 10 x 10 11 x 11 11 x 11 11 x 11 11 x 11 12x11 DriveType No Speeds Direct 2 Direct 2 Direct 2 Direct 2 Direct 2 Direct 2 No Motors 1 1 1 1 1 1 Motor HP Standard Oversized 33...

Страница 12: ...ed No Motors 1 1 1 1 1 Motor HP Standard Oversized 1 00 2 0012 2 00 3 00 2 00 3 00 2 00 3 00 3 00 5 00 Motor RPM Standard Oversized 1750 1750 1750 1750 1750 3450 Motor Frame Size 56 56 56 56 56 Filter...

Страница 13: ...sized 48 48 48 48 48 48 48 48 Belt Drive Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal No Used 1 1 1 Diameter xWidth in 11 x 11 11 x 11 11 x 11 DriveType No Speeds Belt Variable Speed 6...

Страница 14: ...3 00 5 00 Motor RPM Standard Oversized 1750 1750 1750 1750 3450 Motor Frame Size 56 56 56 56 Filters Type Furnished 9 Throwaway Throwaway Throwaway Throwaway No Size Recommended in 4 16 x 25 x 2 4 20...

Страница 15: ...red indoor fan heat To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 1 Gross Cooling Capacities MBH 3 Ton Single Three Phase TSC036A1 A3...

Страница 16: ...red indoor fan heat To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 4 Gross Cooling Capacities MBH 5 Ton Single Three Phase TSC060A1 A3...

Страница 17: ...To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC SensibleHeatCapacity Table PD 6 Gross Cooling Capacities MBH 7 Ton Three Phase Single Compressor TSC090A3 A4 AW AK Ambi...

Страница 18: ...105 2 105 2 105 2 105 2 107 8 95 4 NOTES 1 All capacities shown are gross and have not considered indoor fan heat To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC Sensib...

Страница 19: ...06 7 106 7 106 7 106 7 116 9 80 7 90 124 5 124 5 124 9 124 9 128 4 91 9 122 9 122 9 122 6 122 6 127 2 95 7 119 3 119 3 119 3 119 3 123 3 97 3 114 3 114 3 114 3 114 3 118 3 99 2 75 114 1 106 4 120 6 73...

Страница 20: ...nsidered indoor fan heat To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 10 Gross Cooling Capacities MBH 3Ton THC036A1 A3 A4 AW AmbientT...

Страница 21: ...dered indoor fan heat To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 13 Gross Cooling Capacities MBH 5Ton Three Phase THC060A3 A4 AW Am...

Страница 22: ...6 5 50 7 50 7 54 9 43 7 61 1 34 8 48 1 48 1 51 5 41 9 57 4 33 0 90 58 8 58 8 61 5 54 4 68 1 45 3 56 3 56 3 58 5 52 7 64 8 43 6 53 7 53 7 55 3 50 9 61 3 41 9 51 0 51 0 52 0 49 1 57 5 40 1 75 56 8 46 5...

Страница 23: ...heat To obtain net cooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC SensibleHeatCapacity Table PD 16 Gross Cooling Capacities MBH 7 Ton Three Phase THC092A3 A4 AW AmbientTemperature F...

Страница 24: ...ooling subtract indoor fan heat 2 MBH Total Gross Capacity 3 SHC SensibleHeatCapacity Table PD 18 Gross Cooling Capacities MBH 10Ton Three Phase THC120A3 A4 AW AmbientTemperature F 85 95 105 115 Enter...

Страница 25: ...6 96 2 80 9 107 6 64 0 90 109 9 109 9 113 9 103 3 126 4 86 1 105 6 105 6 108 7 100 5 120 7 83 4 101 1 101 1 101 1 101 1 114 5 80 6 96 2 96 2 97 5 92 3 107 9 77 6 75 104 9 87 8 117 1 67 4 130 2 46 6 99...

Страница 26: ...0 99 0 41 0 91 0 47 1080 0 78 0 38 0 55 0 29 0 96 0 43 0 87 0 39 1140 0 74 0 39 0 47 0 29 0 93 0 44 0 82 0 40 3 TSC036A 1200 0 71 0 40 0 39 0 30 0 89 0 45 0 79 0 41 Downflow 1260 0 65 0 41 0 31 0 30 0...

Страница 27: ...not be affected 1 HPStandardMotor Field Supplied High Static Drive 2 Table PD 22 Belt Drive Evaporator Fan Performance 3 Ton TSC036A3 A4 AW Horizontal Airflow External Static Pressure Inches ofWater...

Страница 28: ...229 1 29 1920 1172 1 23 1205 1 31 1236 1 39 Table PD 24 Continued External Static Pressure Inches ofWater 1 10 1 20 1 30 1 40 1 50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1 HPStandardMotor Drive 1...

Страница 29: ...RPM BHP RPM BHP RPM BHP 1 HPStandardMotor Drive 1600 1117 0 97 1150 1 04 1183 1 11 1215 1 18 1244 1 25 1800 1167 1 16 1 199 1 24 1230 1 31 1259 1 39 1289 1 47 2000 1216 1 37 1249 1 47 2200 2400 Table...

Страница 30: ...2 HPFanMotorHeat MBH 3 000xFanBHP 5000 1 FieldSuppliedFanSheaveAK84andBeltAX34required Table PD 28 Belt Drive Evaporator Fan Performance 6 Ton TSC072A3 A4 AW Horizontal Airflow External Static Pressu...

Страница 31: ...torsas shown in our tabular data will not result in nuisance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 30 Belt Drive Evaporator Fan Performance 6 Ton TSC072 AK...

Страница 32: ...sance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 32 Continued External Static Pressure Inches ofWater 1 10 1 20 1 30 1 40 1 50 1 60 1 70 1 80 1 90 2 00 CFM RPM...

Страница 33: ...shown in our tabular data will not result in nuisance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 34 Continued External Static Pressure Inches ofWater 1 10 1 20...

Страница 34: ...nsareincludedinpressuredropdata RefertoTablePD 54todetermineadditionalstaticpressuredrop duetootheroptions accessories 3 HPFanMotorHeat MBH 2 900xFanBHP 475 5 HPFanMotorHeat MBH 2 950xFanBHP 470 1 Fie...

Страница 35: ...1 20 960 0 79 0 36 0 56 0 28 0 94 0 38 0 82 0 35 1020 0 74 0 37 0 54 0 28 0 90 0 39 0 82 0 36 1080 0 70 0 38 0 49 0 29 0 87 0 41 0 79 0 38 1140 0 66 0 39 0 42 0 29 0 82 0 43 0 74 0 40 3 THC036A 1200 0...

Страница 36: ...s warranty will not be affected 1 HPStandardMotor Field Supplied High Static Drive 2 Table PD 39 Belt Drive Evaporator Fan Performance 3 Ton THC036A3 A4 AW Horizontal Airflow External Static Pressure...

Страница 37: ...1211 1 25 1241 1 32 1920 1186 1 26 1218 1 34 1249 1 42 Table PD 41 Belt Drive Evaporator Fan Performance 4 Ton THC048A3 A4 AW Horizontal Airflow External Static Pressure Inches ofWater 10 20 30 40 50...

Страница 38: ...00 1226 1 48 2400 PD 43 Continued External Static Pressure Inches ofWater 1 10 1 20 1 30 1 40 1 50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1 HPStandardMotor Drive 1000 985 0 56 1021 0 62 1058 0 68...

Страница 39: ...5 Ton THC060A3 A4 AW Horizontal Airflow Dehumidification Hot Gas Reheat External Static Pressure Inches ofWater 10 20 30 40 50 60 70 80 90 1 00 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM...

Страница 40: ...0 1137 1 70 1168 1 81 1201 1 92 1232 2 03 1261 2 14 1291 2 26 2640 1065 1 59 1097 1 71 1129 1 82 1161 1 93 1192 2 05 1223 2 16 1252 2 27 2880 1099 1 80 1130 1 93 1159 2 05 1188 2 18 1217 2 30 2 HP Ove...

Страница 41: ...tabular data will not result in nuisance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 49 Belt Drive Evaporator Fan Performance 7 Ton THC092A3 A4 AW Horizontal Ai...

Страница 42: ...rsas shown in our tabular data will not result in nuisance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 51 Belt Drive Evaporator Fan Performance 8 Ton THC102A3 A4...

Страница 43: ...fanmotorsas shown in our tabular data will not result in nuisance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 53 Continued External Static Pressure Inches ofWate...

Страница 44: ...own in our tabular data will not result in nuisance tripping or premature motor failure Ourproduct swarrantywillnotbeaffected Table PD 55 Belt Drive Evaporator Fan Performance 10 Ton THC120A3 A4 AW Ho...

Страница 45: ...PD 58 Oversized Motor Drive Sheave Fan Speed Rpm Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn Tons Model No Open Open Open Open Open Open Closed 6 T C072A3 A4 AW N A 958 1022 1086 1150 1214 1278 7 TS...

Страница 46: ...045 053 1800 09 2000 0 06 10 0 10 0 18 0 07 0 18 0 02 056 070 083 2200 12 2400 0 09 14 0 14 0 26 0 10 0 26 0 04 081 100 120 1920 0 04 0 07 0 10 0 01 0 06 0 02 0 02 0 011 0 021 6 T C072A 2400 0 06 0 09...

Страница 47: ...14 30 48 82 8 70 29 70 7 50 25 61 2 3 25 11 10 3 25 11 10 TSC060AK 10 90 37 23 2 5 45 18 61 5 45 18 61 14 4 49 18 2 7 20 24 59 7 20 24 59 9 00 30 73 1 9 00 30 73 T C072A3 A4 AW 18 00 61 45 1 18 00 61...

Страница 48: ...2 16 9 16 6 2200 16 8 16 6 16 4 16 2 16 0 15 7 15 4 2400 15 6 15 4 15 2 15 1 14 9 14 6 14 3 10Tons 35 40 45 50 55 60 65 2000 26 0 26 5 26 9 27 4 27 9 28 3 28 6 2400 23 5 24 1 24 7 25 3 25 9 26 4 26 9...

Страница 49: ...ven day programming Keyboard selection of Heat Cool Fan Auto or On All programmable sensors have System On Heat Cool Service LED indicators as standard Night Setback Sensors have one 1 Occupied one 1...

Страница 50: ...53 47 3 60 49 0 60 N A N A TSC060A3 187 253 31 5 50 33 2 50 30 3 45 5 TSC060A4 414 506 16 0 25 16 3 25 15 6 25 TSC060AW 517 633 12 2 15 12 8 20 11 8 15 TSC060AK 342 418 19 6 30 TSC072A3 187 253 32 7 5...

Страница 51: ...3 29 4 45 31 5 50 N A N A THC048A3 187 253 21 2 30 23 3 35 22 6 35 4 THC048A4 414 506 11 0 15 12 6 15 11 8 15 THC048AW 517 633 8 3 15 9 1 15 8 5 15 THC060A1 187 253 39 5 60 41 2 60 N A N A THC060A3 18...

Страница 52: ...9 50 60 52 5 59 5 60 60 BAYHTRR306A 4 5 6 0 1 31 5 31 5 50 50 33 2 33 2 50 50 BAYHTRR312A 9 0 12 0 2 39 0 43 9 50 50 41 1 46 0 50 50 5 TSC060A3 BAYHTRR318A 13 1 17 4 2 53 1 60 1 60 70 55 3 62 3 60 70...

Страница 53: ...0 BAYHTRR406A 6 0 1 12 8 20 14 4 20 4 TSC048A4 BAYHTRR412A 12 0 2 20 1 25 22 1 25 BAYHTRR418A 17 4 2 28 3 30 30 3 35 BAYHTRR406A 6 0 1 16 0 25 16 3 25 BAYHTRR412A 12 0 2 21 6 25 22 0 25 5 TSC060A4 BAY...

Страница 54: ...24 3 25 BAYHTRRW23A 23 0 2 30 3 35 31 0 35 BAYHTRSW09A 9 0 1 13 0 20 14 0 20 6 TSC072AW BAYHTRSW18A 18 0 1 23 8 25 24 8 25 BAYHTRSW27A 27 0 2 34 6 35 35 6 40 BAYHTRSW36A 36 0 2 45 4 50 46 4 50 BAYHTR...

Страница 55: ...306A 4 5 6 0 1 25 3 25 3 35 35 4 TSC048A3 BAYHTRR312A 9 0 12 0 2 37 5 42 4 40 45 BAYHTRR318A 13 1 17 4 2 51 6 58 6 60 60 BAYHTRR306A 4 5 6 0 1 30 3 30 3 45 45 BAYHTRR312A 9 0 12 0 2 37 5 42 4 45 45 5...

Страница 56: ...0 23 3 25 1 35 35 4 THC048A3 BAYHTRR312A 9 0 12 0 2 35 8 40 6 40 45 38 4 43 3 40 45 BAYHTRR318A 13 1 17 4 2 49 9 56 9 50 60 52 5 59 5 60 60 BAYHTRR306A 4 5 6 0 1 30 0 30 0 45 45 31 7 31 7 45 45 BAYHTR...

Страница 57: ...HTRR412A 12 0 2 21 6 25 22 0 25 BAYHTRR418A 17 4 2 29 8 30 30 1 35 BAYHTRR423A 23 0 2 38 3 40 38 6 40 BAYHTRS409A 9 0 1 17 5 25 18 1 25 6 THC072A4 BAYHTRS418A 18 0 1 30 3 35 31 0 35 BAYHTRS427A 27 0 2...

Страница 58: ...1 11 8 15 12 4 15 BAYHTRRW12A 12 0 2 17 1 20 17 8 20 5 THC060AW BAYHTRRW18A 17 4 2 23 6 25 24 3 25 BAYHTRRW23A 23 0 2 30 3 35 31 0 35 BAYHTRSW09A 9 0 1 13 5 20 14 3 20 6 THC072AW BAYHTRSW18A 18 0 1 2...

Страница 59: ...ic Heat Single Point Connection Optional Belt Drive High Efficiency Belt Drive Indoor Motor To Use Heater Heater Control Max Fuse Size Or Tons With Model No kW Rating1 Stages MCA Max Circuit Breaker2...

Страница 60: ...72AK 1 380 3 2 0 4 9 35 0 T C090A3 1 208 230 3 2 00 6 30 48 00 1 208 230 3 3 00 9 40 83 00 T C090A4 1 460 3 2 00 3 10 24 00 1 460 3 3 00 4 60 42 00 T C090AW 1 575 3 2 00 2 50 18 20 1 575 3 3 00 3 70 3...

Страница 61: ...1 70 1 54 3 60 TSC072AK 1 380 3 6 3450 12 2 70 1 1 75 2 5 7 7 TSC090A3 1 208 230 3 7 5 3450 26 0 172 1 1 70 3 85 9 30 TSC090A4 1 460 3 7 5 3450 13 6 90 1 1 70 2 50 5 80 TSC090AW 1 575 3 7 5 3450 10 9...

Страница 62: ...8 230 3 5 7 3450 20 7 156 1 1 70 3 85 9 30 6 THC072A4 1 460 3 5 7 3450 10 75 1 1 70 2 50 5 80 THC072AW 1 575 3 5 7 3450 8 2 54 1 1 70 1 54 3 60 THC092A3 2 208 230 3 3 5 3 3 3450 12 4 12 4 88 88 1 1 70...

Страница 63: ...OTHERS ROOFTOP UNIT ZONE SENSOR OR THERMOSTAT Zone Sensors Typical Number OfWires A Manual Changeover 4 Manual Auto Changeover 5 Manual Auto Changeover with Status Indication LED s 10 Programmable Nig...

Страница 64: ...64 RT PRC005 EN Dimensional Data All dimensions are in inches millimeters 5Tons High Efficiency 3 5Tons Standard Efficiency 3 and 4Tons High Efficiency 3 5Tons...

Страница 65: ...5 RT PRC005 EN Dimensional Data All dimensions are in inches millimeters HorizontalAirflow Supply Return DownflowAirflow Supply Return Through the Base Utilities Unit Clearance and Roof Opening 3 5Ton...

Страница 66: ...66 RT PRC005 EN Dimensional Data All dimensions are in inches Downflow Duct Connections Field Fabricated 3 5Tons 37 1 8 928 MM...

Страница 67: ...67 RT PRC005 EN 6 10Tons Dimensional Data All dimensions are in inches 6Tons Standard and High Efficiency 7 Tons Standard Efficiency 7 Tons High Efficiency 8 and 10Tons Standard and High Efficiency...

Страница 68: ...Tons Dimensional Data All dimensions are in inches 6 10Tons DownflowAirflow Supply and Return Through the Base Utilities 6 10Tons HorizontalAirflow Supply and Return 6 10Tons Unit Clearance and Roof O...

Страница 69: ...69 RT PRC005 EN 6 10Tons Dimensional Data All dimensions are in inches 6 10Tons Roof Curb ALL FLANGES 1 1 4 31 MM 6 10Tons Downflow Duct Connections Field Fabricated...

Страница 70: ...s Accessories Dimensional Data All dimensions are in inches Economizer Manual or Motorized FreshAir Damper See Page 65 for Through the Base Utilities Information Barometric Relief Damper Hood Swing Di...

Страница 71: ...dimensions are in inches 6 10Tons Economizer and Barometric Relief Damper Hoods 6 10Tons Power Exhaust 6 10Tons Swing Diameter for Hinged Door s Option 6 10Tons Options Accessories See Page 68 for Th...

Страница 72: ...294 233 159 207 39 22 TSC120A 1052 909 306 241 164 197 40 21 10 THC120A 1125 982 323 253 178 229 39 22 NOTES 1 Corner weights are given for information only 2 Weights are approximate TableW 2 Factory...

Страница 73: ...plate voltage Crankcase heater internal temperature and current sensitive motor overloads shall be included for maximum protection Compressors shall have internal spring isolation and sound muffling t...

Страница 74: ...r is a status indicator readable throughTracer orTracker This option is available for microprocessor controlled units Oversized Motors Factory or field installed direct drive oversized motors shall be...

Страница 75: ...energy savings potential than the standard dry bulb control This is due to the additional wet bulb sensing capability This option shall be available for microprocessor controlled units It can be fiel...

Страница 76: ...com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice Literature Order Number File Number Supersedes Stoc...

Отзывы: