33
RT-PRC005-EN
(8½ Ton)
Standard Efficiency
Performance
Data
Table PD-33— Belt Drive Evaporator Fan Performance — 8½-Ton — TSC102A3,A4,AW, AK —DownflowAirflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Field Supplied
2-HP Standard Motor
Low Static Drive (1
)
& Drive
2720
—
—
—
—
—
—
613
0.60
655
0.72
695
0.84
733
0.95
769
1.08
802
1.21
833
1.34
3060
—
—
—
—
611
0.64
650
0.74
688
0.85
725
0.98
761
1.11
796
1.25
828
1.38
861
1.52
3400
—
—
612
0.68
651
0.79
689
0.91
724
1.02
759
1.15
792
1.29
825
1.43
856
1.58
887
1.72
3740
622
0.76
659
0.86
693
0.97
729
1.10
764
1.23
795
1.35
826
1.49
857
1.64
887
1.79
916
1.96
4080
671
0.96
706
1.08
738
1.19
770
1.32
804
1.46
834
1.60
864
1.74
892
1.88
920
2.04
948
2.20
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to stnadard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table PD-33 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Drive
3-HP Oversized Motor & Drive
2720
863
1.48
892
1.63
920
1.78
946
1.93
973
2.08
999
2.24
1025
2.39
1050
2.55
1073
2.71
1098
2.88
3060
891
1.66
919
1.81
946
1.96
973
2.12
999
2.29
1024
2.46
1048
2.63
1072
2.80
1096
2.98
1119
3.14
3400
917
1.87
946
2.03
974
2.18
1001
2.34
1026
2.52
1051
2.69
1074
2.86
1099
3.05
1121
3.23
1143
3.41
3740
945
2.11
974
2.28
1001
2.44
1028
2.61
1054
2.78
1079
2.96
1103
3.14
1126
3.32
—
—
—
—
4080
976
2.38
1002
2.56
1029
2.73
1055
2.91
1081
3.09
1105
3.26
1130
3.45
—
—
—
—
—
—
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
Table PD-34 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Drive
3-HP Oversized Motor & Drive
2720
956
1.67
982
1.79
1008
1.91
1033
2.03
1056
2.14
1079
2.26
1102
2.38
1125
2.50
1146
2.62
1168
2.74
3060
999
1.99
1026
2.12
1052
2.26
1078
2.39
1101
2.52
1124
2.66
1146
2.79
1168
2.92
1188
3.05
1209
3.18
3400
1034
2.32
1067
2.49
1094
2.64
1120
2.79
1145
2.94
1168
3.09
1191
3.24
1213
3.39
—
—
—
—
3740
1063
2.63
1098
2.84
1129
3.03
1158
3.21
1185
3.39
—
—
—
—
—
—
—
—
—
—
4080
1093
2.99
1125
3.19
1157
3.40
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Table PD-34 — Belt Drive Evaporator Fan Performance — 8½-Ton — TSC102A3,A4,AW, AK —Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HP Standard Motor & Field Supplied
2-HP Standard Motor & Drive
Low Static Drive (1
)
2720
—
—
598
0.57
646
0.67
689
0.78
734
0.90
781
1.04
826
1.18
865
1.31
898
1.44
928
1.56
3060
616
0.69
654
0.77
693
0.86
735
0.98
773
1.10
812
1.23
855
1.39
897
1.55
934
1.70
969
1.85
3400
675
0.92
711
1.01
743
1.10
781
1.22
819
1.36
853
1.49
886
1.62
925
1.79
964
1.97
1000
2.14
3740
735
1.20
770
1.30
799
1.40
830
1.51
865
1.65
899
1.79
930
1.94
960
2.09
994
2.26
1028
2.44
4080
796
1.53
828
1.65
857
1.76
883
1.86
913
1.99
945
2.15
977
2.30
1006
2.47
1034
2.63
1061
2.79
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. Field Supplied Fan Sheave AK79 and Belt AX38 required.
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.