![Trane Precedent RT-PRC005 Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/trane/precedent-rt-prc005/precedent-rt-prc005_user-manual_1149464029.webp)
29
RT-PRC005-EN
(5 Ton)
Standard Efficiency
Performance
Data
Table PD-25— Belt Drive Evaporator Fan Performance — 5 Ton — TSC060A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1
)
1600
674
0.33
735
0.39
786
0.45
835
0.50
883
0.56
928
0.63
972
0.70
1011
0.77
1048
0.84
1084
0.90
1800
743
0.46
801
0.52
849
0.59
894
0.65
937
0.70
979
0.77
1021
0.85
1060
0.93
1098
1.01
1134
1.09
2000
813
0.61
866
0.68
914
0.76
956
0.83
995
0.89
1035
0.96
1073
1.02
1111
1.10
1147
1.19
1183
1.28
2200
886
0.80
933
0.87
980
0.96
1019
1.03
1057
1.11
1093
1.18
1129
1.25
1164
1.33
1198
1.40
1233
1.50
2400
959
1.03
1000
1.10
1045
1.19
1085
1.28
1121
1.36
1154
1.45
1188
1.53
1221
1.60
—
—
—
—
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range of our
fan motors as shown in our tabular data will not
result in nuisance tripping or premature motor
failure. Our product’s warranty will not be
affected.
Table PD-25 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1600
1117
0.97
1150
1.04
1183
1.11
1215
1.18
1244
1.25
1800
1167
1.16
1199
1.24
1230
1.31
1259
1.39
1289
1.47
2000
1216
1.37
1249
1.47
—
—
—
—
—
—
2200
—
—
—
—
—
—
—
—
—
—
2400
—
—
—
—
—
—
—
—
—
—
Table PD-26 — Belt Drive Evaporator Fan Performance — 5 Ton — TSC060A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1
)
1600
746
0.39
812
0.47
876
0.54
934
0.62
985
0.70
1032
0.77
1074
0.85
1117
0.93
1157
1.01
1196
1.09
1800
824
0.54
883
0.62
940
0.70
996
0.79
1048
0.88
1094
0.96
1137
1.05
1176
1.14
1214
1.22
1252
1.31
2000
902
0.72
957
0.80
1008
0.90
1059
0.99
1110
1.09
1157
1.19
1200
1.28
1239
1.38
1276
1.47
1311
1.50
2200
981
0.93
1032
1.03
1080
1.13
1126
1.23
1173
1.34
1219
1.44
—
—
—
—
—
—
—
—
2400
1061
1.19
1109
1.29
1153
1.40
1196
1.50
—
—
—
—
—
—
—
—
—
—
—
—
For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range of our
fan motors as shown in our tabular data will not
result in nuisance tripping or premature motor
failure. Our product’s warranty will not be
affected.
Table PD-26 — Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Drive
1600
1232
1.18
1267
1.26
1299
1.35
1332
1.45
—
—
1800
1289
1.41
1323
1.50
—
—
—
—
—
—
2000
—
—
—
—
—
—
—
—
—
—
2200
—
—
—
—
—
—
—
—
—
—
2400
—
—
—
—
—
—
—
—
—
—