56
RT-PRC005-EN
Electrical
Data
(High Efficiency)
Table ED-7 — Unit Wiring With Electric Heat (Single Point Connection) — 208/230 Volts — High Efficiency
Standard Indoor Motor
Oversize Indoor Motor
To Use
Heater
Heater
Control
Max Fuse Size Or
Max Fuse Size Or
Tons
With
Model No.
kW Rating
1
Stages
MCA
Max Circuit Breaker
2
MCA
Max Circuit Breaker
2
208/230 Volts Single Phase
BAYHTRR105A
3.8/5.0
1
25.5/28.9
40/40
28.5/31.9
40/40
3
THC036A1
BAYHTRR110A
7.5/10.0
2
48.0/55.0
50/60
51.0/58.0
60/60
BAYHTRR114A
10.4/13.8
2
65.1/74.8
70/80
68.1/77.8
70/80
BAYHTRR105A
3.8/5.0
1
29.4/30.5
45/45
31.5/33.1
50/50
BAYHTRR110A
7.5/10.0
2
49.6/56.6
50/60
52.3/59.3
60/60
4
THC048A1
BAYHTRR114A
10.4/13.8
2
66.8/76.4
70/80
69.4/79.0
70/80
BAYHTRR118A
13.2/17.6
2
84.0/96.1
90/100
86.6/98.8
90/100
BAYHTRR105A
3.8/5.0
1
39.5/39.5
60/60
41.2/41.2
60/60
BAYHTRR110A
7.5/10.0
2
52.9/59.9
60/60
55.0/62.0
60/70
5
THC060A1
BAYHTRR114A
10.4/13.8
2
70.0/79.6
80/80
72.1/81.8
80/90
BAYHTRR118A
13.2/17.6
2
87.3/99.4
90/100
89.4/101.5
90/100
208/230 Volts Three Phase
BAYHTRR306A
4.5/6.0
1
18.5/20.9
25/25
21.5/23.9
25/25
3
THC036A3
BAYHTRR312A
9.0/12.0
2
34.1/39.0
35/40
37.1/42.0
40/45
BAYHTRR318A
13.1/17.4
2
48.3/55.3
50/60
51.3/58.3
60/60
BAYHTRR306A
4.5/6.0
1
21.2/22.5
30/30
23.3/25.1
35/35
4
THC048A3
BAYHTRR312A
9.0/12.0
2
35.8/40.6
40/45
38.4/43.3
40/45
BAYHTRR318A
13.1/17.4
2
49.9/56.9
50/60
52.5/59.5
60/60
BAYHTRR306A
4.5/6.0
1
30.0/30.0
45/45
31.7/31.7
45/45
BAYHTRR312A
9.0/12.0
2
39.0/43.9
45/45
41.1/46.0
45/50
5
THC060A3
BAYHTRR318A
13.1/17.4
2
53.1/60.1
60/70
55.3/62.3
60/70
BAYHTRR323A
17.3/23.0
2
67.8/76.9
70/80
69.9/79.0
70/80
BAYHTRS309A
6.8/9.0
1
34.8/34.8
50/50
35.7/35.7
50/50
6
THC072A3
BAYHTRS318A
13.5/18.0
1
53.1/60.4
60/70
54.8/62.0
60/70
BAYHTRS327A
20.3/27.0
2
76.6/87.5
80/90
78.3/89.1
80/90
BAYHTRS336A
27.0/36.0
2
100.1/114.5
110/125
101.8/116.1
110/125
BAYHTRT309A
6.8/9.0
1
38.1/38.1
50/50
44.2/44.2
50/50
7½
THC092A3
BAYHTRT318A
13.5/18.0
1
54.8/62.0
60/70
58.6/65.9
60/70
BAYHTRT327A
20.3/27.0
2
78.3/89.1
80/90
82.1/93.0
90/100
BAYHTRT336A
27.0/36.0
2
101.8/116.1
110/125
105.6/120.0
110/125
BAYHTRT309A
6.8/9.0
1
42.3/42.3
50/50
44.2/44.2
50/50
8½
THC102A3
BAYHTRT318A
13.5/18.0
1
54.8/62.0
60/70
58.6/65.9
60/70
BAYHTRT327A
20.3/27.0
2
78.3/89.1
80/90
82.1/93.0
90/100
BAYHTRT336A
27.0/36.0
2
101.8/116.1
110/125
105.6/120.0
110/125
BAYHTRT318A
13.5/18.0
1
58.6/65.9
60/70
63.6/70.9
70/80
10
THC120A3
BAYHTRT327A
20.3/27.0
2
82.1/93.0
90/100
87.1/98.0
90/100
BAYHTRT336A
27.0/36.0
2
105.6/120.0
110/125
110.6/125.0
125/125
BAYHTRT354A
40.6/54.0
2
152.5/141.7
175/150
157.5/146.7
175/150
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.